05.05 Start-Up
SIEMENS AG 6RX1700-0AD76 7-21
SIMOREG DC Master Operating Instructions
As from configuration software D7-SYS V4.0 R07/98, it is possible to configure not only one,
but two communications modules (CBC, CBD, CBP2) for module T400. These modules are
then located on an ADB in slots G (1. CB) and F (2. CB).
In this case, the 2
nd
CB is not configured with parameters of the basic device, but the CB
parameters must be configured as modifiable parameters of the T400.
Possible communications paths are shown in the figure below. For details of how to
configure a T400, please consult the relevant documentation (e.g. SIMADYN D –
Configuring Instructions T400, 6DD1903-0EA0 etc.).
BASEBOARD TECHBOARD
Configuration channel
to COMBOARD
Setpoint ch annel
Actual value channel
Parameter channel
BASEBOARD
Parameter channel
TECHBOARD
Warning ch annel
from COMBOARD
1st COMBOARD
Dual-port RAMDual-port RAM
2nd COMBOARD
Dual-port RAM
Parameter channel from
operator panel on CUD1
Warning ch annel
from TECHBOARD
Fault channel
from TECHBOARD
CUD1 - module of the
SIMOREG DC Masters
6RA70
FB-@DRIVE
Receiver
FB-CRV
FB-PTRANS transfers parameters
Transmitter
FB-CTV
Transmitter
FB-CTV
Receiver
FB-CRV
FB@DRIVE (BBF=0)
processes parameters
for number ranges
1000 to 1999 and
3000 to 3999
Receiver
FB-CRV
Transmitter
FB-CTV
Parameter
channel
Setpoints
Actual
values
lokal USS slave
interface
FB@DRIVE (BBF=0)
processes parameters
for number ranges
1000 to 1999 and
3000 to 3999
Receiver
FB-CRV
Transmitter
FB-CTV
FB-CBCONF
Configuration of the 1st COMBOARD using
CB parameters U710 to U72
Receiv er
FB-CRV
Transmitter
FB-CTV
Parameter
channel
Setpoints
Actual
values
lokal USS slave
interface
Configuration channel
to COMBOARD
Setpoint channel
Actual value channel
Parameter channel
BASEBOARD
Parameter channel
TECHBOARD
Warning channel
from COMBOARD
Configuration channel
to COMBOARD
Setpoint channel
Actual value channel
Parameter channel
BASEBOARD
Parameter channel
TECHBOARD
Warning channel
from COMBOARD
FB-TFAW
receives
and
transmits
alarm and
warning
messages
The SIMOREG DC Master 6RA70 does not permit direct evaluation of the signals of a pulse
generator connected to the terminals of the CUD1 by the T400.