05.05 Connectors and binectors
SIEMENS AG 6RX1700-0AD76 12-1
SIMOREG DC Master Operating Instructions
12 List of connectors and binectors
12.1 Connector list
The values of connectors can be displayed via parameters r041, r042, r043 and P044.
The following numeric representation applies to all connectors:
In the internal software representation, 100% corresponds to the number 4000 hex = 16384 dec. The
value range is -200.00% ... +199.99%, corresponding to 8000 hex ... 7FFF hex. The connectors are
transferred via the serial interfaces in this internal mode of representation.
100% corresponds to converter rated quantities r072.i02 (currents, armature), r073.i02 (currents,
field), P078.i01 (line voltages, armature).
The following numeric representation applies to all double-word connectors:
In the internal software representation, 100% corresponds to the number 4000 0000 hex =
16384*65536 dec.
The value range is -200.00% ... +199.9999999%, corresponding to -2
31
dec ... +(2
31
- 1) dec or
8000 0000 hex ... 7FFF FFFF hex.
If a double-word connector is the input of a connector selection parameter, or if a connector is the
input of a double-word connector selection parameter, this may be equivalent to division or
multiplication by the value 65536. For details of the connection to double-word connectors, see
Section 9.1, "The following rules apply to the selection of double-word connectors“.
Connector Description Normalization Function
diag., Sheet
Fixed values
K0000
Fixed value 0
G120
K0001
Fixed value 100.00%
16384
=
∧
100%
G120
K0002
Fixed value 200.00%
16384
=
∧
100%
G120
K0003
Fixed value -100.00%
16384
=
∧
100%
G120
K0004
Fixed value -200.00%
16384
=
∧
100%
G120
K0005
Fixed value 50.00%
16384
=
∧
100%
G120
K0006
Fixed value 150.00%
16384
=
∧
100%
G120
K0007
Fixed value -50.00%
16384
=
∧
100%
G120
K0008
Fixed value -150.00%
16384
=
∧
100%
G120
K0009
Fixed value 0 or special function specified in each case
Analog inputs
K0010
Analog input, terminal 4 / 5 (main setpoint)
Raw value after A/D conversion (unfiltered, not normalized)
16384
=
∧
100%
G113
K0011
Analog input, terminal 4 / 5 (main setpoint)
After normalization, offset injection, filtering
16384
=
∧
100%
G113
K0012
Analog input, terminal 103 / 104 (main actual value)
Raw value after A/D conversion (unfiltered, not normalized)
16384
=
∧
100%
G113
K0013
Analog input, terminal 103 / 104 (main actual value)
After normalization, offset injection, filtering
16384
=
∧
100%
G113
K0014
Analog input, terminal 6 / 7 (analog selectable input 1)
Raw value after A/D conversion (unfiltered, not normalized)
16384
=
∧
100%
G113
K0015
Analog input, terminal 6 / 7 (analog selectable input 1)
After normalization, offset injection, filtering
16384
=
∧
100%
G113
K0016
Analog input, terminal 8 / 9 (analog selectable input 2)
Raw value after A/D conversion (unfiltered, not normalized)
16384
=
∧
100%
G114
K0017
Analog input, terminal 8 / 9 (analog selectable input 2)
After normalization, offset injection, filtering
16384
=
∧
100%
G114
K0018
Analog input, terminal 10 / 11 (analog selectable input 3)
Raw value after A/D conversion (unfiltered, not normalized)
16384
=
∧
100%
G114