EasyManua.ls Logo

Siemens 6RA7086-6KS22

Siemens 6RA7086-6KS22
734 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
05.05 Function descriptions
SIEMENS AG 6RX1700-0AD76 9-35
SIMOREG DC Master Operating Instructions
9.15.2 Configuring for dynamic overload capability
Section 9.15.3 provides the following information for each converter model:
Maximum overload period
t
an
for starting with cold power section and specified constant overload
with an overload factor of X (i.e. loading with X times the converter rated DC current * P077) (see
small table at top right)
Maximum current interval
t
ab
(maximum cooling time) until the power section reaches the "cold"
state (see below small table at top right)
Limit characteristics fields for calculating overload capability
in thermally settled, intermittent
overload operation (periodic load cycles).
(In tabulated form: Top left
As curve with logarithmic y axis: Curve at bottom left
As curve with linear y axis: Curve at bottom right)
Important
:
The power section is in the "cold" state when the calculated thyristor temperature corresponds to less
than 5 % of its maximum permissible value. This state can be scanned via a binary selectable output.
Note:
If load cycles are started with a cold power section at least slightly within the specified load cycle
limits, then the thermally settled state can be reached without tripping the I
2
t monitor.
If the I
2
t monitoring function is parameterized for a shutdown response (P075 = 2), the converter
should not be allowed to operate too close to the limit characteristic when periodic load cycles are
configured with a load cycle time of longer or slightly shorter or equal to 300 s.
In all other cases, and especially when parameterizing reduction of the armature current setpoint
(P075 = 1) as the I
2
t monitoring trip response, it is possible to fully utilize the maximum overload
capability defined by the limit characteristic.
Structure of limit characteristics fields for intermittent overload duty:
Each characteristics field refers to a load cycle of intermittent overload operation with a total period
of
300 s.
This type of load cycle consists of two periods,
i.e. the base-load duty period
(armature actual current P077 * converter rated DC current)
and the overload period
(actual armature current P077 * converter rated DC current).
Each limit characteristic displays the maximum permissible overload period Tp
over
the maximum base-load current Ig for a specific overload factor X for each converter model.
For the remainder
of the load cycle, the current may not exceed the base-load current as defined by
the overload factor.
If no limit characteristic is specified for a particular overload factor, then the characteristic for the next-
higher overload factor must be applied.
The limit characteristics fields apply to a load cycle time of 300s.
For load cycle times of < 300s, the overload period must be reduced proportionally (load cycle/300s).
For load cycle times of > 300s, the overload period is the same as that for a cycle time of 300s, but the
base-load period is correspondingly longer.
The limit characteristics fields apply for a setting of P077 = 1.00. If P077 is set to 1.00, i.e. in the
case of thermal derating, the currents which actually flow must be weighted with a factor of 1/P077:
Overload factor X for characteristic =
Actual overload current
P converter rated DC current077*
Actual maximum base-load current = P077 * max. base-load current acc. to character-
istic in % of converter rated DC current

Table of Contents

Related product manuals