Function diagrams 05.05
8-46 SIEMENS AG 6RX1700-0AD76
SIMOREG DC Master Operating Instructions
Sheet G174 Peer-to-peer interface 3
.01
.02
.03
.04
.05
RS485
M
+
10 10
87564321
- G174 -
1
0
1
0
<1>
<2>
61
62
63
64
65
Tx+
Tx-
Rx+/Tx+
Rx-/Tx-
M
G-SST3
X162
015
.01
.16
CUD2
[G169.6]
[G182.6]
[G151.3]
[G183.6]
1s
P805.001 (0)
P819 (1)
B
P818 (1)
B
P800 (0)
P807 (0,000s)
P803 (13)
P801 (2)
r809
P808 (9030)
B
B9031
B9030
K9001
K9005
K9004
K9003
K9002
Bit 0 ... Bit 15
B9100
B9200
B9300
B9400
B9500
B9115
B9215
B9315
B9415
B9515
U118 (0)
B
B
K9020
K
K
P804
K
K
K
32
167
0
33
0
Binector / connector
converter
r814.01 to .05 r815.01 to .05
Peer-to-peer interface 3
Receive data Transmit data
Peer-to-peer On/Off
Baud rate
No. of Words (1...5)
Parameters for peer-to-peer interface:
Telegram monitoring time
Peer-to-peer diagnostic parameter
Word 1
Word 2
Word 3
Word 4
Word 5
Fault signal trip
1 = "Telegram
monitoring
timeout"
Bus terminator
1 = "Fault F013"
every 16Bits
from preceding
drive
to following
drive
<1> Binector = 0:
Output drivers are high resistance
<2> Binector = 0:
Telegram sign-of-life monitoring is not active
Enable data send
Enable Data receive
Word 1
Word 2
Word 3
Word 4
Word 5
FS
For transmission of double-word connectors see Section 9.13.2
See also connector type converter on sheet G169