12
Protection Self-Monitoring
7UT51 v3
122 PRIM-2330C
12.5 Events and Actions
This table describes the events that control and are
generated by the self-monitoring features of the relay.
They are listed in numerical order by their event
identification number (shown in the “Event” column).
The text in the “LCD Abbreviation” column is the
corresponding text that will appear when viewing logs
on the front panel LCD display. In the “Oper” column, a
letter “C” or “G” indicates that the “Coming” and/or
“Going” events are logged in the Operational Log,
while if in the “Fault” column they indicate that the
events are logged in the open fault log. A letter in the
“In/Out” column indicates that the event can control an
LED and/or signal contact (“S”), and/or control a trip
(command) contact (“T”).
Table 12.1
Events Related to Protection Self
-
Monitoring
Protection Self
-
Monitoring Occurrence LCD Abbreviation Event Oper Fault In/Out
Internal Self
-
Monitoring (see Section 12.2 on page 119)
Relay is operational and at least one protection function is active.
(This event is always marshalled to signal contact 5, and can be
marshalled to other contacts as well.)
Relay OK 0051 CG S
LEDs have been reset LED Reset 0005 C
Parameters are being set SetChg inProg 0095 CG S
Wrong version of internal software
Wrong internal device identification
Wrong SW
-
vers
Wrong dev. ID
0100
0101
C
C
Annunciations lost (Operational Log buffer overflow)
Annunciations for PC lost
Fault annunciations lost (buffer overflow of a Fault Log)
Operational annunciations invalid
Fault annunciations invalid
LED annunciations buffer invalid
VDEW state invalid
Annunc. lost
Annu. PC lost
Flt.Buff.Over
Oper.Ann.Inva
Flt.Ann.Inval
LED Buff.Inva
VDEW
-
StateInv
0110
0111
0115
0120
0121
0124
0129
C
C
C
C
C
C
G
G
G
G
C
Checksum error in memory
Checksum error in parameter set A
Checksum error in parameter set B
Checksum error in parameter set C
Checksum error in parameter set D
Chksum Error
ChksumA Error
ChksumB Error
ChksumC Error
ChksumD Error
0135
0136
0137
0138
0139
C
C
C
C
C
G
G
G
G
G
Failure of 24VDC internal power supply circuit
Failure of 15VDC internal power supply circuit
Failure of 5VDC internal power supply circuit
24 V Failure
15 V Failure
5 V Failure
0141
0143
0144
C
C
C
G
G
G
S
S
S
Analog/digital converters (offset failure) Offset Fail 0145 CG S
Failure of I/O Module 1 (ZEA)
Failure of I/O Module 2 (ZEA, 7UT513 only)
Failure of RKA Module
LSA (data communication interface) disrupted
I/O 1 Failure
I/O 2 Failure
RKA Failure
LSA disrupted
0151
0152
0154
0159
C
C
C
C
G
G
G
G
S
S
Monitoring of Supply Power (Section 12.3 on page 120)
Failure of the supply power de
-
energizes the Self
-
Monitor signal
relay.
Monitoring of CT Circuits (Section 12.4 on page 120)
Failure of current summation monitoring (only available when the
protected object is a bus)
I Supervision 0161 S
Failure of current symmetry for at least one winding (or branch)
Failure of current symmetry for Winding 1 (or branch 1)
Failure of current symmetry for winding 2 (or branch 2)
Failure of current symmetry for winding 3 (or branch 3) (7UT513
only)
Failure Isymm
Fail. Isym 1
Fail. Isym 2
Fail. Isym 3
0163
0571
0572
0573
C
C
C
C
G
G
G
G
S
S
S
S