EasyManuals Logo

Siemens 7UT51 User Manual

Siemens 7UT51
232 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #43 background imageLoading...
Page #43 background image
7UT51 v3
Transformer Differential Protection (87T and 87HS)
4
PRIM-2330C 43
Figure 4.5
Typical CT Wiring for a Three
-
Winding, Delta
-
Wye
-
Delta Transformer
4.2 Describing the
Transformer
This section describes the addresses used to provide
the relay with information about the protected
transformer, including:
The number of windings the transformer has
The rated frequency of the protected transformer
The rated phase-to-phase voltage (V
n
) of each
winding of the protected transformer
The rated apparent power (VA) of each winding of
the protected transformer
The phase shift (lag angle relative to Winding 1) of
winding 2 (and, if applicable, of winding 3) of the
protected transformer
In the following discussion, “Winding 1” is the
reference winding, which is usually the high-side
winding of the protected transformer. If a CT is
installed in the ground lead of a grounded wye
connected transformer, that winding must be used as
the reference winding in order to ensure increased
ground-fault sensitivity by correction of the zero
sequence current.
Primary
Secondary
Tertiary
7UT513
a
a'
A
b
b'
B
c
c'
C
I
A
I
B
I
C
I
a
I
a'
I
b
I
b'
I
c
I
c'
3A1
3A2
2A1
2A2
1A1
1A2
3B1
3B2
2B1
2B2
1B1
1B2
3D1
3D2
2C1
2C2
1C1
1C2

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens 7UT51 and is the answer not in the manual?

Siemens 7UT51 Specifications

General IconGeneral
BrandSiemens
Model7UT51
CategoryRelays
LanguageEnglish

Related product manuals