EasyManua.ls Logo

Siemens 7UT51

Siemens 7UT51
232 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
7 Ground Differential Protection (87N)
7UT51 v3
92 PRIM-2330C
Figure 7.3
Ground Differential Protection of a Delta
Winding with a Shunt Reactor
7.1 Calculated Quantities
The restraining current,
I
R
, is the scalar sum of the
separate amplitudes of the measured phase and
ground currents. It is a measure of the total amount of
current flowing through the transformer, regardless of
whether the currents are balanced. It is calculated
according to equation 7.1 and equation 7.2:
(7.1)
(7.2)
where
N
is the number of samples taken during each
power system cycle, while
i
A
(
k
),
i
B
(
k
),
i
C
(
k
), and
i
G
(
k
)
are the sampled and normalized values of the phase
and ground currents.
The fundamental vector of the ground current,
I
G
, is
calculated using Fourier analysis:
(7.3)
(7.4)
(7.5)
Two calculated current vectors, and , are the major
components of the algorithm:
(7.6)
(7.7)
Both quantities are calculated using the
Fourier-analysis algorithm described in equation 7.3,
equation 7.4, and equation 7.5.
The differential current,
I
D
, is by definition the
amplitude of the vector-difference of the measured
ground current and the calculated zero sequence
current. By convention, any current flowing into the
protected equipment is considered to have a positive
magnitude; so
I
D
is calculated using the following
equation:
(7.8)
Figure 7.4
Trip Area for I*o/Io**=1
)()()()()(
kikikikiki
G
CBAR
+++=
=
=
1
0
)(
1
)(
N
k
RR
kni
N
nI
()
)2cos()(
2
)(Re
1
0
N
k
kni
N
nI
N
k
GG
π
=
=
()
)2sin()(
2
)(Im
1
0
N
k
kni
N
nI
N
k
GG
π
=
=
0.0
0.2
0.4
0.6
0.8
1.0
1.2
0 30 60 90 120 150 180
1/
**
0
*
0
=
II
4.06
2.04
1.37
*
0
I
I
OP
ϕ
(degrees)
k
0
= 1.03
CLASSICAL
TRIP AREA
EXTENDED TRIP AREA
BLOCK
AREA

Table of Contents

Related product manuals