This 7UT51 (version 3) settings worksheet enables
easy recording of 7UT51 parameter settings when
configuring the relay. The settings are listed in
numerical sequence based on Address just as they
appear on the LCD. Where applicable, value ranges
are provided for easy reference. Only configurable
settings are listed.
Before configuring the device, copy this form and
enter the device identification number as well as the
date of configuration. Then simply mark an X beside
the desired options and enter numerical values in the
blank spaces provided. The factory defaults appear in
a column. Where different ranges and defaults apply
for the 1 amp and 5 amp nominal relays, the 1 amp
values are in parentheses below the 5 amp values.
After entering all data on this configuration form, take it
to the device and enter the information into the relay.
This form allows for the recording of all four setting
groups. Be sure to file a copy of this worksheet for
future reference.
Addr
LCD Line 1
WinDIGSI Description
Options or
Range and Unit
Default
Setting
Group A
Setting
Group B
Setting
Group C
Setting
Group D
1100
TRANSFORMER DATA
To configure 11xx settings, setting 7801 must first be set to one of the transformer types.
1102
Vn WIND 1
Rated voltage of transformer Winding 1
0.4
-
800.0 kV 110.0
1103
VA WIND 1
Rated apparent power (VA) of Winding 1
0.2
-
5000.0 MVA 38.1
1104
In CT WND1
Rated primary current of Winding 1 CT
1
-
100000 A 200
1105
CT1 STARPT
Star
-
point formation of Winding 1 CT
Towa rds
Transformer
X
Towards line/busbar
1106
Io1PROCESS
Processing of Winding 1 zero sequence
current
Io
-
elimination X
Io
-
correction
WITHOUT
1107
In CT STP1
Rated prim. current of Winding 1 star
-
point
CT
1
-
100000 A 200
1108
CT1 GND
-
PT
Ground point formation of wind. 1
star
-
point CT
Towa rds t r ansfo r mer X
Towards ground
1121
VECTOR GR2
Vector group associated with winding 2
0
-
11 0
1122
Vn WIND 2
Rated voltage of transformer winding 2
0.4
-
800.0 kV 11.0
1123
VA WIND 2
Rated apparent power (VA) of winding 2
0.2
-
5000.0 MVA 38.1
1124
In CT WND2
Rated primary current of winding 2 CT
1
-
100000 A 2000
1125
CT2 STARPT
Star
-
point formation of winding 2 CT
Towa rds t r ansfo r mer X
Towards line/busbar
1126
Io2PROCESS
Processing of winding 2 zero sequence
current
Io
-
elimination X
Io
-
correction
WITHOUT
1127
In CT STP2
Rated prim. current of winding 2 star
-
point
CT
1
-
100000 A 2000