EasyManua.ls Logo

Siemens ACCESS 9340 - Meter with Integrated Display Communications Setup

Siemens ACCESS 9340
264 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
© 2008 Siemens Energy & Automation, Inc. All Rights Reserved.
PMCM-9340D-0208 ACCESS 9340 and 9360 Meters
2/2008 Chapter 3—Operation
EN–17
Meter With Integrated Display Communications Setup
Table 31: Communications Default Settings
Communications Setting Default
Protocol MB.RTU (Modbus RTU)
Address 1
Baud Rate 9600
Parity Even
1. Press ###: until COMMS
(communications) is visible.
2. Press COMMS (communications).
3. Select the protocol: MB.RTU (Modbus
RTU), Jbus, MB. A.8 (Modbus ASCII 8
bits), MB. A.7 (Modbus ASCII 7 bits).
4. Press OK.
5. Enter the ADDR ( meter address).
6. Press OK.
7. Select the BAUD (baud rate).
8. Press OK.
9. Select the parity: EVEN, ODD, or NONE.
10. Press OK.
11. Press
1; until you are asked to save your
changes.
12. Press YES to save the changes.


  






PLSD110100

Table of Contents

Related product manuals