ACCESS 9340 and 9360 Meters PMCM-9340D-0208
Chapter 4—Metering Capabilities 2/2008
EN–52
Energy Readings
The meter calculates and stores accumulated energy values for real
and reactive energy (kWh and kVARh) both into and out of the load,
and also accumulates absolute apparent energy. Table 43 lists the
energy values the meter can accumulate.
Table 43: Energy Readings
Energy Reading, 3-Phase Reportable Range Shown on the Display
Accumulated Energy
Real (Signed/Absolute)
Reactive (Signed/Absolute)
Real (In)
Real (Out)
Reactive (In)
Reactive (Out)
Apparent
-9,999,999,999,999,999 to
9,999,999,999,999,999 Wh
-9,999,999,999,999,999 to
9,999,999,999,999,999 VARh
0 to 9,999,999,999,999,999 Wh
0 to 9,999,999,999,999,999 Wh
0 to 9,999,999,999,999,999 VARh
0 to 9,999,999,999,999,999 VARh
0 to 9,999,999,999,999,999 VAh
0000.000 kWh to 99,999.99 MWh
and
0000.000 to 99,999.99 MVARh
Accumulated Energy, Conditional
Real (In)
Real (Out)
Reactive (In)
Reactive (Out)
Apparent
0 to 9,999,999,999,999,999 Wh
0 to 9,999,999,999,999,999 Wh
0 to 9,999,999,999,999,999 VARh
0 to 9,999,999,999,999,999 VARh
0 to 9,999,999,999,999,999 VAh
Not shown on the display.
Readings are obtained only
through the communications link.
Accumulated Energy, Incremental
Real (In)
Real (Out)
Reactive (In)
Reactive (Out)
Apparent
0 to 999,999,999,999 Wh
0 to 999,999,999,999 Wh
0 to 999,999,999,999 VARh
0 to 999,999,999,999 VARh
0 to 999,999,999,999 VAh
Not shown on the display.
Readings are obtained only
through the communications link.
Reactive Energy
Quadrant 1
Quadrant 2
Quadrant 3
Quadrant 4
0 to 999,999,999,999 VARh
0 to 999,999,999,999 VARh
0 to 999,999,999,999 VARh
0 to 999,999,999,999 VARh
Not shown on the display.
Readings are obtained only
through the communications link.
Not shown on the meter display.

Table of Contents