PMCM-9340D-0208 ACCESS 9340 and 9360 Meters
2/2008 Chapter 8—Logging
EN–97
Data Logs
The ACCESS 9340 records and stores readings at regularly
scheduled intervals in one independent data log. The ACCESS 9360
records and stores meter readings at regularly scheduled intervals in
up to three independent data logs. Some data log files are
preconfigured at the factory. You can accept the preconfigured data
logs or change them to meet your specific needs. You can set up
each data log to store the following information:
• Timed Interval—1 second to 24 hours for Data Log 1, and 1
minute to 24 hours for Data Logs 2 and 3 (how often the values
are logged)
• First-In-First-Out (FIFO) or Fill and Hold
• Values to be logged—up to 96 registers along with the date and
time of each log entry
• START/STOP Time—each log has the ability to start and stop at
a certain time during the day
The default registers for Data Log 1 are listed in Table 8–5 below.