Power Factor Sign Conventions
The meter can be set to one of two power factor sign conventions:
IEEE or IEC. The ACCESS 9340/9360 defaults to the IEEE power
factor sign convention. Figure 4–2 illustrates the two sign
conventions. For instructions on changing the power factor sign
convention, refer to “Advanced Meter Setup Options” on page 26.
Figure 4–2: Power factor sign convention
Real
Power
In
watts negative (–)
vars positive (+)
power factor (–)
watts positive (+)
vars positive (+)
power factor (+)
watts negative (–)
vars negative (–)
power factor (–)
watts positive (+)
vars negative (–)
power factor (+)
IEC Power Factor Sign Convention
Reverse
Power Flow
Normal
Power Flow
Reactive
Power In
Quadrant
2
Quadrant
1
Quadrant
3
Quadrant
4
watts negative (–)
vars positive (+)
power factor (+)
watts positive (+)
vars positive (+)
power factor (–)
watts negative (–)
vars negative (–)
power factor (–)
watts positive (+)
vars negative (–)
power factor (+)
Reactive
Power In
Real
Power
In
IEEE Power Factor Sign Convention
Reverse
Power Flow
Normal
Power Flow
Quadrant
2
Quadrant
1
Quadrant
3
Quadrant
4
Figure 4–3: Power Factor Display Example
L`abNSQ
TU LMcK [)ZS\
LRLd\
NNNe
d
f
g
h
h
h
h
The power
factor sign is
visible next to
the power factor
reading.