ACCESS 9340 and 9360 Meters PMCM-9340D-0208
Chapter 8—Logging 2/2008
EN–94
Memory Allocation for Log Files
Each file in the meter has a maximum memory size. Memory is not
shared between the different logs, so reducing the number of values
recorded in one log will not allow more values to be stored in a
different log. The following table lists the memory allocated to each
log:
Table 8–3: Memory Allocation for Each Log
Log Type
Max. Records
Stored
Max. Register
Values Recorded
Storage
(Bytes)
Meter
Model
Alarm Log 100 11 2,200 All models
Maintenance Log 40 4 320 All models
Billing Log 5000 96 + 3 D/T 65,536
9340
9360
Data Log 1 5000 96 + 3 D/T 14,808
9340
9360
Data Log 2 5000 96 + 3 D/T 393,216 9360
Data Log 3 5000 96 + 3 D/T 393,216 9360