EasyManua.ls Logo

Siemens ACCESS 9340 - Setpoint-Driven Alarms

Siemens ACCESS 9340
264 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
© 2008 Siemens Energy & Automation, Inc. All Rights Reserved.
PMCM-9340D-0208 ACCESS 9340 and 9360 Meters
2/2008 Chapter 6—Basic Alarms
EN–73
Setpoint-driven Alarms
Many of the alarm conditions require that you define setpoints. This
includes all alarms for over, under, and phase unbalance alarm
conditions. Other alarm conditions such as digital input transitions
and phase reversals do not require setpoints. For those alarm
conditions that require setpoints, you must define the following
information:
Pickup Setpoint
Pickup Delay
Dropout Setpoint
Dropout Delay
NOTE: Alarms with both Pickup and Dropout setpoints set to zero are
invalid.
To understand how the meter handles setpoint-driven alarms, see
Figure 62 on page 74. Figure 61 shows what the actual alarm Log
entries for Figure 62 might look like, as displayed by WinPM.Net.
NOTE: The software does not actually display the codes in
parentheses—EV1, EV2, Max1, Max2. These are references to the
codes in Figure 62.
Figure 61: Sample alarm log entry
PLSD110219
EV1 Max1
EV2 Max2

Table of Contents

Related product manuals