ACCESS 9340 and 9360 Meters PMCM-9340D-0208
Chapter 6—Basic Alarms 2/2008
EN–80
Table 6–2: Scale Groups
Scale Group Measurement Range Scale Factor
Scale Group A—Phase Current
Amperes
0–327.67 A –2
0–3,276.7 A –1
0–32,767 A 0 (default)
0–327.67 kA 1
Scale Group B—Neutral Current
Amperes
0–327.67 A –2
0–3,276.7 A –1
0–32,767 A 0 (default)
0–327.67 kA 1
Scale Group D—Voltage
Voltage
0–3,276.7 V –1
0–32,767 V 0 (default)
0–327.67 kV 1
0–3,276.7 kV 2
Scale Group F—Power kW, kVAR, kVA
Power
0–32.767 kW, kVAR, kVA –3
0–327.67 kW, kVAR, kVA –2
0–3,276.7 kW, kVAR, kVA –1
0–32,767 kW, kVAR, kVA 0 (default)
0–327.67 MW, MVAR, MVA 1
0–3,276.7 MW, MVAR, MVA 2
0–32,767 MW, MVAR, MVA 3