Engineering via SICAM WEB
400 Unrestricted SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual
DC8-037-2.02, Edition 10.2017
Type Predefined Assignment
Double information to double command
(1-pole):
DI-610x with DO-6200
DI IOM xIN D00/D01 ... command IOM y – OUT D00/D01
DI IOM xIN D02/D03 ... command IOM y – OUT D02/D03
DI IOM xIN D04/D05 ... command IOM y – OUT D04/D05
DI IOM xIN D06/D07 ... command IOM y – OUT D06/D07
DI IOM xIN D10/D11 ... command IOM y – OUT D10/D11
DI IOM xIN D12/D13 ... command IOM y – OUT D12/D13
DI IOM xIN D14/D15 ... command IOM y – OUT D14/D15
DI IOM xIN D16/D17 ... command IOM y – OUT D16/D17
Double information to double command
(1-pole):
DI-610x with DO-6212
(2 DO-6212 with 1 DI-610x possible)
DI IOM xIN D00/D01 ... command IOM y – OUT D00/D01
DI IOM xIN D02/D03 ... command IOM y – OUT D02/D03
DI IOM xIN D04/D05 ... command IOM y – OUT D04/D05
DI IOM xIN D06/D07 ... command IOM y – OUT D06/D07
DI IOM xIN D10/D11 ... command IOM z – OUT D00/D01
DI IOM xIN D12/D13 ... command IOM z – OUT D02/D03
DI IOM xIN D14/D15 ... command IOM z – OUT D04/D05
DI IOM xIN D16/D17 ... command IOM z – OUT D06/D07
Double information to double command
(1-pole):
DI-610x with DO-6230
DI IOM xIN D00/D01 … command IOM y – CA00/CA01
DI IOM xIN D02/D03 ... command IOM y – CA02/CA03
DI IOM xIN D04/D05 ... command IOM y – CA04/CA05
DI IOM xIN D06/D07 ... command IOM y – CA06/CA07
DI IOM xIN D10/D11 ... command IOM y – CB00/CB01
DI IOM xIN D12/D13 ... command IOM y – CB02/CB03
DI IOM xIN D14/D15 ... command IOM y – CB04/CB05
DI IOM xIN D16/D17 ... command IOM y – CB06/CB07
Double information to double command
(1.5-pole):
DI-610x with DO-6212
(2 DO-6212 with 1 DI-610x possible)
DI IOM xIN D00/D01 ... command IOM y – OUT D00/D01
DI IOM xIN D02/D03 ... command IOM y – OUT D02/D03
DI IOM xIN D04/D05 ... command IOM y – OUT D04/D05
DI IOM xIN D10/D11 ... command IOM z – OUT D00/D01
DI IOM xIN D12/D13 ... command IOM z – OUT D02/D03
DI IOM xIN D14/D15 ... command IOM z – OUT D04/D05
Double information to double command
(1.5-pole):
DI-610x with DO-6230
DI IOM xIN D00/D01 … command IOM y – CA00/CA01
DI IOM xIN D02/D03 ... command IOM y – CA02/CA03
DI IOM xIN D04/D05 ... command IOM y – CA04/CA05
DI IOM xIN D06/D07 ... command IOM y – CA06/CA07
DI IOM xIN D10/D11 ... command IOM y – CB00/CB01
DI IOM xIN D12/D13 ... command IOM y – CB02/CB03
DI IOM xIN D14/D15 ... command IOM y – CB04/CB05
DI IOM xIN D16/D17 ... command IOM y – CB06/CB07
Double information to double command
(2-pole):
DI-610x with DO-6212
(2 DO-6212 with 1 DI-610x possible)
DI IOM xIN D00/D01 ... command IOM y – OUT D00..D03
DI IOM xIN D04/D05 ... command IOM y – OUT D04..D07
DI IOM xIN D10/D11 ... command IOM z – OUT D00..D03
DI IOM xIN D14/D15 ... command IOM z – OUT D04..D07
Double information to double command
(2-pole):
DI-610x with DO-6230
DI IOM xIN D00/D01 ... command IOM y – CA00..CB01
DI IOM xIN D02/D03 ... command IOM y – CA02..CB03
DI IOM xIN D04/D05 ... command IOM y – CA04..CB05
DI IOM xIN D06/D07 ... command IOM y – CA06..CB07
x = 0..7, y = x+1, z = x+2
Note
In each case the module DO-62xx must be equipped directly after the module DI-610x.