Engineering via SICAM WEB
SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual Unrestricted 401
DC8-037-2.02, Edition 10.2017
I/O Master Module with Firmware USIO81
Type Predefined Assignment
Single information to single command
(1-pole):
DI-810x m with it DO-820x
EM IOM x – IN D00 ... command IOM y OUT D00
EM IOM x – IN D01 ... command IOM y OUT D01
: :
EM IOM x – IN D07 ... command IOM y OUT D07
Single information to single command
(1-pole):
DI-811x with DO-821x
(2 DO-8212 with 1 DI-811x possible)
EM IOM x – IN D00 ... command IOM y OUT D00
EM IOM x – IN D01 ... command IOM y OUT D01
: :
EM IOM x – IN D07 ... command IOM y OUT D07
EM IOM x – IN D10 ... command IOM z OUT D00
EM IOM x – IN D11 ... command IOM z OUT D01
: :
EM IOM x – IN D17 ... command IOM z OUT D07
Single information to single command
(1,5-pole):
DI-810x with DO-820x
EM IOM x – IN D00 ... command IOM y OUT D00
EM IOM x – IN D01 ... command IOM y OUT D01
: :
EM IOM x – IN D06 ... command IOM y OUT D06
Single information to single command
(1,5-pole):
DI-811x with DO-821x
(2 DO-821x with 1 DI-811x possible)
EM IOM x – IN D00 ... command IOM y OUT D00
EM IOM x – IN D01 ... command IOM y OUT D01
: :
EM IOM x – IN D06 ... command IOM y OUT D06
EM IOM x – IN D10 ... command IOM z OUT D00
EM IOM x – IN D11 ... command IOM z OUT D01
: :
EM IOM x – IN D16 ... command IOM z OUT D06
Single information to single command
(2-pole):
DI-810x with DO-820x
EM IOM x – IN D00 ... command IOM y – OUT D00/D01
EM IOM x – IN D02 ... command IOM y – OUT D02/D03
EM IOM x – IN D04 ... command IOM y – OUT D04/D05
EM IOM x – IN D06 ... command IOM y – OUT D06/D07
Single information to single command
(2-pole):
DI-811x with DO-821x
(2 DO-821x with 1 DI-811x possible)
EM IOM x – IN D00 ... command IOM y – OUT D00/D01
EM IOM x – IN D02 ... command IOM y – OUT D02/D03
EM IOM x – IN D04 ... command IOM y – OUT D04/D05
EM IOM x – IN D06 ... command IOM y – OUT D06/D07
EM IOM x – IN D10 ... command IOM z – OUT D00/D01
EM IOM x – IN D12 ... command IOM z – OUT D02/D03
EM IOM x – IN D14 ... command IOM z – OUT D04/D05
EM IOM x – IN D16 ... command IOM z – OUT D06/D07
Double information to double command
(1-pole):
DI-810x with DO-820x
DM IOM x – IN D00/D01 ... command IOM y – OUT D00/D01
DM IOM x – IN D02/D03 ... command IOM y – OUT D02/D03
DM IOM x – IN D04/D05 ... command IOM y – OUT D04/D05
DM IOM x – IN D06/D07 ... command IOM y – OUT D06/D07
Double information to double command
(1-pole):
DI-811x with DO-821x
(2 DO-821x with 1 DI-811x possible)
DM IOM x – IN D00/D01 ... command IOM y – OUT D00/D01
DM IOM x – IN D02/D03 ... command IOM y – OUT D02/D03
DM IOM x – IN D04/D05 ... command IOM y – OUT D04/D05
DM IOM x – IN D06/D07 ... command IOM y – OUT D06/D07
DM IOM x – IN D10/D11 ... command IOM z – OUT D00/D01
DM IOM x – IN D12/D13 ... command IOM z – OUT D02/D03
DM IOM x – IN D14/D15 ... command IOM z – OUT D04/D05
DM IOM x – IN D16/D17 ... command IOM z – OUT D06/D07
Double information to double command
(1,5-pole):
DI-810x with DO-820x
DM IOM x – IN D00/D01 ... command IOM y – OUT D00/D01
DM IOM x – IN D02/D03 ... command IOM y – OUT D02/D03
DM IOM x – IN D04/D05 ... command IOM y – OUT D04/D05
Double information to double command
(1,5-pole):
DI-811x with DO-821x
(2 DO-821x with 1 DI-811x possible)
DM IOM x – IN D00/D01 ... command IOM y – OUT D00/D01
DM IOM x – IN D02/D03 ... command IOM y – OUT D02/D03
DM IOM x – IN D04/D05 ... command IOM y – OUT D04/D05
DM IOM x – IN D10/D11 ... command IOM z – OUT D00/D01
DM IOM x – IN D12/D13 ... command IOM z – OUT D02/D03
DM IOM x – IN D14/D15 ... command IOM z – OUT D04/D05