Commissioning (software)
5.7 Commissioning modes
Control Units CU240S
5-54 Operating Instructions, 11/2006, A5E00766042B AA
Manual Download of a parameter set with an MMC
Note
The following important restrictions should be considered when using the download
procedure:
During the download the inverter will not react to any commands.
Once the download procedure has started, it cannot be interrupted.
After upload and download of parameters between differing Control Units, parameter
settings must be checked.
Parameter download from a different CU might fail with F0063 if parameters cannot be
downloaded (Check P949 for the (first) parameter number which cannot be downloaded).
If the download fails, the inverter reverts to the previous parameters from the EEPROM.
Prerequisites
Supply voltage is active for the download inverter
The download inverter is in "Ready State".
Parameter Description (Parameter name and factory setting (if not variable) in bold) Setting
Insert the MMC to the download inverter and perform the manual download according the flow
chart.
P0010 = 30 Commissioning parameter*
0: Ready
1: Quick commissioning
2: Inverter
30: Factory setting, parameter transfer
95: Safety commissioning (for CUs with fail-safe functions only)
P0804 = ? Select Clone file (for download)
0: clone00.bin
99: clone99.bin
P0803 = 2 Transfer data to EEPROM
0: Disabled
1: Start OP Transfer
2: Start MMC Transfer
If the download has been completed successfully, P0010 and P0803 will be set to 0 and the
"RDY" LED is on.
If the upload has failed, F0061 (MMC-PS not fitted) or F0062 (MMC-PS contents invalid) resp.
F0063 (MMC-PS contents incompatible) will be displayed, LED "SF" (red) is on.
In this case insert a proper MMC and attempt another download or perform a factory reset.
After a successful manually download remove the MMC from inverter and insert it to the next
download inverter. Then perform the download steps again until the series commissioning has
been completed for all inverters.

Table of Contents

Other manuals for Siemens CU240S DP-F

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens CU240S DP-F and is the answer not in the manual?

Siemens CU240S DP-F Specifications

General IconGeneral
BrandSiemens
ModelCU240S DP-F
CategoryControl Unit
LanguageEnglish

Related product manuals