449/617
Building Technologies Division User Manual LMS14… CC1U7471en
6 The settings in detail 28.01.2015
Line no.
Operating line
1610 Nominal setpoint
1612 Reduced setpoint
1620 Release
24h/day ¦ Time programs HCs ¦ Time program 4/DHW
1630 Charging priority
Absolute ¦ Shifting ¦ None ¦ MC shifting, PC absolute
1640 Legionella function
Off ¦ Periodically ¦ Fixed weekday
1641 Legionella funct periodically
1642 Legionella funct weekday
Monday ¦ Tuesday ¦ Wednesday ¦ Thursday ¦ Friday ¦ Saturday ¦ Sunday
1644 Legionella funct time
1645 Legionella funct setpoint
1646 Legionella funct duration
1647 Legionella funct circ pump
Off ¦ On
1660 Circulating pump release
Time program 3/HC3 ¦ DHW release ¦ Time program 4/DHW ¦ Time program 5
1661 Circulating pump cycling
Off ¦ On
1663 Circulation setpoint
1680 Optg mode changeover
None ¦ Off ¦ On
Consumer circuit 1
1859 Flow temp setp cons request
1874 DHW charging priority
No ¦ Yes
1875 Excess heat draw
Off ¦ On
1878 With buffer
No ¦ Yes
1880 With prim contr/system pump
No ¦ Yes
Consumer circuit 2
1909 Flow temp setp cons request
1924 DHW charging priority
No ¦ Yes
1925 Excess heat draw
Off ¦ On
1928 With buffer
No ¦ Yes
1930 With prim contr/system pump
No ¦ Yes
Swimming pool circuit
1959
Flow temp setpoint
1974 DHW charging priority
No ¦ Yes
1975 Excess heat draw
Off ¦ On
1978 With buffer
No ¦ Yes
1980 With prim contr/system pump
No ¦ Yes
Swimming pool