201/267 
Building Technologies   Basic documentation LMV37.4...  CC1P7546en 
  27 Parameter level  17.12.2018 
 
reset
 
P
Vh
mi n
s%
Bild 97/0707
Press 
reset
 to go to editing mode. 
 
 or   
P
Vh
mi n
s%
Bild 98/0707
Press   or   to select the required  
setting. 
 
Example: 3 for gas modulating with pilot valve 
(Gp2 mod) 
 
reset
 
P
Vh
mi n
s%
Bild 161/0807
Press 
reset
 to save the selected setting. 
 
ESC
 
P
Vhmins%
Bild 99/0707
Press 
ESC
 to return to the parameter level. 
 
To the next parameter 
 
 
reset
 
P
Vh
s
mi n %
Bild 100/0807
Press 
reset
 to change to parameter 542: to  
activate the VSD / PWM fan. 
You can choose: 
0 = VSD / PWM fan OFF 
1 = VSD / PWM fan ON 
 
To the next parameter 
Back to the previous  
parameter 
 
 
P
V
h
s
mi n %
Bild 101/0807
Press    to change to parameter 641: to 
control speed standardization of the VSD. 
You can choose: 
0 = speed standardization of VSD OFF 
1 = speed standardization of VSD ON 
After setting speed standardization to 1, 
standardization of the VSD commences. If 
successful, the parameter is reset to 0. 
Negative values indicate errors (refer to chapter 
Automatic speed standardization). 
 
To the next parameter 
 
 
  For operating modes 1…4, 7…10, 12…16 and 19…22, refer to chapter Setting curvepoints P0 and 
P9 for modulating mode («G mod», «Gp1 mod», «Gp2 mod» and «Lo mod») 
  For operating modes 5, 6, 11, 17 and 18, refer to chapter Setting the curvepoints for multistage mode  
(«Lo 2-stage» and «Lo 3-stage»)