28 Parameter list LMV37.4 17.12.2018
Par. Parameter Number of Type Edit Value range Increment Default Password level
no. elements Min. Max. setting write read
postpurge speed)
0 = inactive
1 = active
2 = active (50% tolerance increase outside operation)
530 Activation trim function
0 = inactive
1 = active
2 = active (including test function for analog input)
3 = active (including ignition speed)
4 = active (including ignition speed and analog input
test)
1 Std_u8 edit 0 4 1 0 OEM HF
542 Activation of VSD / PWM fan
0 = deactivated
1 = active
2 = active (no repetition)
1 Selection edit 0 2 1 0 HF HF
544 Ramp modulating 1 Std_u8 edit 32 s 80 s 1 s 32 s HF HF
545 Lower output limit
undefined = 20%
1 Output edit 20% 100% 0,1% undefined HF (GA) HF (GA)
546 Upper output limit
undefined = 100%
1 Output edit 20% 100% 0,1% Undefined HF (GA) HF (GA)
547 Lower trim limit 1 Std_u16 Edit -15% 0% 0,1% -4% OEM HF (GA)
548 Upper trim limit 1 Std_u16 edit 0% 25% 0,1% 4% OEM HF (GA)
549 Trim damping (based on low-fire) 1 Std_u8 edit 0% 100% 1% 88% OEM HF
550 Trim delay time (after entering phase 60) 1 Std_u8 edit 0 s 255% 1 s 25 s OEM HF
551 Wait time until warning with active trim limit 1 Time edit 0 s 60 min 0,2 s 0 s OEM HF
552 Behavior if maximum trim limitation time is exceeded
0 = Warning message only (trim impact remains
active)
1 = Warning and deactivation of the trim function
2 = Shutdown
1 Std_u8 edit 0 2 1 0 OEM HF
600 Actuators
601 Selection of reference point
Index 0 = fuel
Index 1 = air
Setting values:
2 Selection edit 0 1 1 Index
0
1
Wert
1
0
OEM HF