236/267
Building Technologies Basic documentation LMV37.4... CC1P7546en
28 Parameter list LMV37.4 17.12.2018
Par. Parameter Number of Type Edit Value range Increment Default Password level
no. elements Min. Max. setting write read
936 Standardized speed 1 Std_s16
read only
-200% 200% 0,1% 0% --- IS
942 Active load controller source
1 = output during curve settings
2 = manual output
3 = default output via building automation
4 = default output via analog input
5 = external load controller via contacts
1 Selection
read only
0 255 1 0 --- HF
947 Result of contact sensing (bit-coded)
Bit 0.0 = 1: Pressure switch-min
Bit 0.1 = 2: Pressure switch-max
Bit 0.2 = 4: Pressure switch valve proving
Bit 0.3 = 8 = Air pressure switch
Bit 0.4 = 16: Load controller OPEN
Bit 0.5 = 32: Load controller ON
Bit 0.6 = 64: Load controller CLOSE
Bit 0.7 = 128: Safety loop
Bit 1.0 = 1: Safety valve
Bit 1.1 = 2: Ignition
Bit 1.2 = 4: Fuel valve 1
Bit 1.3 = 8: Fuel valve 2
Bit 1.4 = 16: Fuel valve 3 / pilot valve
Bit 1.5 = 32: Reset
2 Std_u8 read only 0 255 1 0 --- IS
For query
via
ACS410
948 Contact feedback network counter register 14 Std_u8
read only
0 255 1 0 --- HF
950 Required relay state (bit-coded)
Bit 0 = 1: Alarm
Bit 1 = 2: Safety valve
Bit 2 = 4: Ignition
Bit 3 = 8: Fuel valve V1
Bit 4 = 16: Fuel valve V2
Bit 5 = 32: Fuel valve V3 / pilot valve
1 Std_u8
read only
0 255 1 0 --- IS
For query
via
ACS410
951 Mains voltage (normalized)
AC 230 V: Voltage = value x 1.710
AC 120 V: Voltage = value x 0.866
1 Std_u8 read only 0 V 255 V 1 V 0 V --- HF (GA)
954 Intensity of flame 1 Std_u8
read only
0% 100% 1% 0% --- IS
960 Actual flow rate (m³/h, l/h, ft³/h, gal/h) 1 Std_u16
read only
0 6553,5 0,1 0 --- IS
961 Phase (state for external module and display) 1 Std_u8
read only
0 255 1 0 --- IS
For query