250/267
Building Technologies Basic documentation LMV37.4... CC1P7546en
29 Error code list (all LMV2 types / LMV3 types) 17.12.2018
Error
code
Diagnostic code Meaning for the LMV37.4 Recommended measures or causes
1 Pressure switch-max / POC
2 Pressure switch valve proving
/ Fuel selection Fuel 0 / Reset
3 Air pressure switch
4 Fuel selection Fuel 1 / Load
controller OPEN
5 Load controller ON/OFF
6 Fuel selection Fuel 0 / Load
controller CLOSED
7 Safety loop / Burner flange
8 Safety valve
9 Ignition transformer
10 Fuel valve V1
11 Fuel valve V2
12 Fuel valve V3
13 Fuel selection Fuel 1 / Reset
108 # Internal error contact request Make a reset; if error occurs repeatedly, replace the LMV37.4
0 Pressure switch-min
1 Pressure switch-max / POC
2 Pressure switch valve proving
/ Fuel selection Fuel 0 / Reset
3 Air pressure switch
4 Fuel selection Fuel 1 / Load
controller OPEN
5 Load controller ON/OFF
6 Fuel selection Fuel 0 / Load
controller CLOSED
7 Safety loop / Burner flange
8 Safety valve
9 Ignition transformer
10 Fuel valve V1
11 Fuel valve V2
12 Fuel valve V3
13 Fuel selection Fuel 1 / Reset
110 # Internal error voltage monitor test Make a reset; if error occurs repeatedly, replace the LMV37.4
111 # Power failure
Mains voltage to low
Exchange ratio diagnostics code
voltage value (120 V: 0.843 / 230 V: 1,683)
112
0 Mains voltage recovery
Error code for triggering a reset on power restoration (no error)