Building Technologies Basic documentation LMV37.4... CC1P7546en
29 Error code list (all LMV2 types / LMV3 types) 17.12.2018
Error
code
Diagnostic code Meaning for the LMV37.4 Recommended measures or causes
113 # Internal error mains voltage supervision Make a reset; if error occurs repeatedly, replace the LMV37.4
115 # Internal error system counter
116
0 Designed life time exceeded (250´000 startups)
Warning threshold has been reached. The LMV37.4 should be replaced
117
0
Life time exceeded
Operation no longer allowed
Switch-off threshold has been reached
120
0 Interrupt limitation fuel meter input
Too many disturbance pulses at the fuel meters input
Improve EMC
121 # Internal error EEPROM access
Make a reset, repeat last parameterization / check. Restore the parameter set, if error occurs
repeatedly, replace the LMV37.4
122 # Internal error EEPROM access
Make a reset, repeat last parameterization / check. Restore the parameter set, if error occurs
repeatedly, replace the LMV37.4
123 # Internal error EEPROM access
Make a reset, repeat last parameterization / check. Restore the parameter set, if error occurs
repeatedly, replace the LMV37.4
124 # Internal error EEPROM access
Make a reset, repeat last parameterization / check. Restore the parameter set, if error occurs
repeatedly, replace the LMV37.4
125 # Internal error EEPROM read access Make a reset, repeat last parameterization / check. If error occurs repeatedly, replace the LMV37.4
126 # Internal error EEPROM write access Make a reset, repeat last parameterization / check. If error occurs repeatedly, replace the LMV37.4
127 # Internal error EEPROM access
Make a reset, repeat last parameterization / check. Restore the parameter set, if error occurs
repeatedly, replace the LMV37.4
128
0
Internal error EEPROM access - synchronization during
initialization
Make a reset; if error occurs repeatedly, replace the LMV37.4
129 #
Internal error EEPROM access – command
synchronization
Make a reset, repeat last parameterization / check. If error occurs repeatedly, replace the LMV37.4
130 # Internal error EEPROM access - timeout Make a reset, repeat last parameterization / check. If error occurs repeatedly, replace the LMV37.4
131 # Internal error EEPROM access - page on abort Make a reset, repeat last parameterization / check. If error occurs repeatedly, replace the LMV37.4
132 # Internal error EEPROM register initialization Make a reset; if error occurs repeatedly, replace the LMV37.4
133 # Internal error EEPROM access – Request synchronization Make a reset, repeat last parameterization / check. If error occurs repeatedly, replace the LMV37.4
134 # Internal error EEPROM access – Request synchronization Make a reset, repeat last parameterization / check. If error occurs repeatedly, replace the LMV37.4
135 # Internal error EEPROM access – Request synchronization Make a reset, repeat last parameterization / check. If error occurs repeatedly, replace the LMV37.4
136 # Restore
1 Restore started
Restore of a backup has been started (no error)
New LMV37.4 require resetting following restore!
for further diagnostic codes for error code 136, refer to
error code 137
For measures, refer to error code 137
137 # Internal error – backup / restore
157 (-99) Restore – ok, but backup < data set of current LMV37.4
Restore successful, but backup data record is smaller than in the current LMV37.4
239 (-17) Backup – storage of backup in AZL2 faulty
Reset and repeat backup

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens LMV37.4 Series and is the answer not in the manual?

Siemens LMV37.4 Series Specifications

General IconGeneral
BrandSiemens
ModelLMV37.4 Series
CategoryController
LanguageEnglish

Related product manuals