Diagnostics
Inserting a C-PLUG that does not contain the configuration of a compatible device type,
accidentally removing the C-PLUG or general malfunctions of the C-PLUG are signaled by the
diagnostics mechanisms of the IE Switch (LEDs, WEB-based management, SNMP, CLI and
PROFINET diagnostics).
Inserting in the C-PLUG slot on the IE Switch X‑300
Product group Slot Figure C‑PLUG
X-300
X-300M
Rear of the device 1. Remove the screw cover.
2. Insert the C-PLUG in the intended slot.
3. Close the screw cover again correctly.
XR-300M Rear of the device
- right
1. Remove the cover.
2. Insert the C-PLUG in the intended slot.
3. Close the cover again correctly.
X‑300EEC Top of the housing 1. Open the slider.
2. Insert the C-PLUG.
3. Close the slider.
Removing the C-PLUG from the IE Switch X‑300
It is only necessary to remove the C‑PLUG if the IE Switch develops a fault.
Description of the device
4.6 C-PLUG (configuration plug)
SCALANCE X-300
Operating Instructions, 11/2019, A5E01113043-24 95