IO-Link Master
11.1 IO-Link Master (6ES7148-6JA00-0AB0)
ET 200eco PN
Operating Instructions, 08/2016, A5E01250250-AJ
211
Insulation test voltage
• Ethernet interface
1500 V
rms
(IEEE802.3)
• All other circuit elements
707 V DC (type test)
• Between 1L+ and 2L+
Yes
• Between 1L+, channels and all other circuit
elements
No
• Between channels
No
• Between Ethernet and all other circuit ele-
ments
Yes
Status, interrupts, diagnostics
• Group error/maintenance
Red LED / yellow LED "SF/MT"
• Bus monitoring PROFINET IO
Red "BF" LED
• Monitoring of supply voltage 1L+
Green "ON" LED
• Monitoring of supply voltage 2L+
Green "24 V DC" LED
• Existing connection to network
Green "P1 LK" and "P2 LK" LED; LED for
PROFINET IO infeed and loop-through
• IO-Link port
Green LED "IO-L"
• Digital input/digital output
Green LED
• Fault at digital input/digital output
Red LED
• Diagnostic information can be read
Yes
• Missing 2L+
Yes
• Short-circuit of the sensor supply to M
Yes, for Channels 4 to 7, per channel group
• Short-circuit at output (Channel 0 to 3)
Yes, per channel
• Wire break at input
Input current < 0.3 mA per channel
• Wire break at output (Channel 0 to 3)
Yes, in the off state, per channel
Number of sensor supplies
6 (X1-X4 (IO-LINK/DI) and X5-X6 (DI))
Load current 200 mA per output to X1-X4 (IO-LINK/DI)
100 mA per output to X5-X6 (DI)