IO-Link Master
11.1 IO-Link Master (6ES7148-6JA00-0AB0)
ET 200eco PN
212 Operating Instructions, 08/2016, A5E01250250-AJ
Number of ports that can be controlled simulta-
4, in all mounting positions
IO-Link protocol 1.0 Yes
Transmission rate 4.8 kBaud (COM1), 38.4 kBaud (COM2)
Size of the process data, input per port
Size of the process data, input per module
Size of the process data, output per port
Size of the process data, output per module
Number of inputs that can be controlled simulta-
8, in all mounting positions
IO-Link Device selection data (Port 1 to 4)
Connection of IO-Link devices
DQ Yes
Sensor selection data (input signals 0 to 7 only)
Cable length, shielded Max. 30 m
• Nominal value
DC 24 V
• For signal "1"
11 to 30 V
• For signal "0"
-3 to 5 V
Input current
• At signal "1"
Typ. 7 mA
• At "0" to "1"
Typ. 3 ms
• At "1" to "0"
Typ. 3 ms
According to IEC 61131, Type 3
Connection of 2-wire proximity switches
• Permitted quiescent current
Max. 1.5 mA