EasyManua.ls Logo

Siemens SIMATIC ET 200SP - Delay Time and Hysteresis Settings

Siemens SIMATIC ET 200SP
140 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Functions
8.5 Protective functions for data carriers
CPU 1515SP PC (F)
Manual, 05/2017, A5E32701806-AC
79
Console application ewfmgr.exe
The application is called via the Windows command line (Command Prompt).
The following functions are available, among others, for setting, switching on and switching
off the EWF:
Table 8- 2 Enhanced Write Filter functions
Function
Command
Write-protect drive C: Switching on
ewfmgr c: -enable
Write-protect drive C: disable
(modified data is accepted)
ewfmgr c: -commitanddisable
Modified files on drive C: Accept
ewfmgr c: -commit
Display information about the EWF drive
ewfmgr c:
Display help
ewfmgr /h
Note
The EWF commands for write protection become effective only after a restart.
Note
The EWF command ewfmgr c: -commitanddisable
must not be used with the option -
Live
.