Using PID_3Step
5.2 PID_3Step V2
PID control
136 Function Manual, 03/2017, A5E35300227-AC
Result
The actuator is moved in the selected direction. Time measurement will start once the
actuator has reached the first endstop and will end when the actuator reaches this endstop
for the second time. The motor transition time is equal to the time measured divided by two.
The progress and status of transition time measurement are displayed. The transition time
measured is saved in the instance data block on the CPU and displayed in the "Measured
transition time" field. When the transition time measurement is ended and
ActivateRecoverMode = TRUE, PID_3Step switches to the operating mode from which the
transition time measurement was started. If the transition time measurement is ended and
ActivateRecoverMode = FALSE, PID_3Step changes to "Inactive" mode.
Cancelling transition time measurement
PID_3Step switches to "Inactive" mode if you cancel transition time measurement by
pressing the Stop button.

Table of Contents

Other manuals for Siemens SIMATIC S7-1500T

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMATIC S7-1500T and is the answer not in the manual?

Siemens SIMATIC S7-1500T Specifications

General IconGeneral
BrandSiemens
ModelSIMATIC S7-1500T
CategoryController
LanguageEnglish

Related product manuals