Technical data
12.2 Technical data
TP 270, OP 270, MP 270B (WinCC flexible)
Operating Instructions, Edition 03/2004, 6AV6691-1DD01-0AB0
12-7
Backup battery (option)
Type Lithium battery (Sonnenschein SL2361)
Voltage/Capacity
2)
3.6 V / approx. 1.5 Ah
Service life Approx. 4 years
2) All rights reserved
Network connection MP 270B OP 270 / TP 270
Type 1 x Ethernet (10/100 Mbit) Optional via NE 2000-compatible
Ethernet card
Ambient conditions OP 270 6" / TP 270 6"
MP 270B 6" Touch
MP 270B / OP 270 10" /
TP 270 10"
Installation position
Max. permissible angle of inclination
without external ventilation
Vertical
±35°
Vertical
±35°
Max. permissible ambient temperature
Operation
Vertical installation
Installation angled from the
perpendicular to max. 35°
Shipping, storage
0...+50 °C
0...+35 °C
-20...+60 °C
0...+50 °C
0...+40 °C
-20...+60 °C
Shock loading
Operation
Shipping, storage
15 g / 30 ms
25 g / 6 ms
Vibration
Operation
Shipping, storage
0,075 mm (10 - 58 Hz) 1 g (58 - 150 Hz)
3.5 mm (5 - 9 Hz) 1 g (9 - 500 Hz)
Barometric pressure
Operation
Shipping, storage
7951080 hPa
6601080 hPa
Ambient conditions MP 270B Keys / OP 270 MP 270B Touch / TP 270
Relative humidity
Operation, transport, storage
Max. 90%, no condensation
Max. 85%, no condensation