Appendix   
A.2 System alarms 
  TP 270, OP 270, MP 270B (WinCC flexible) 
A-16  Operating Instructions, Edition 03/2004, 6AV6691-1DD01-0AB0 
 
Number Effect/cause Remedy 
190100  The area pointer is not updated because the 
configured address for this area pointer is not 
available. 
Type 
1  Warning alarms 
2  Error alarms 
3  PLC acknowledgment 
4  HMI device acknowledgment 
5  LED mapping 
6  Trend request 
7  Trend transfer 1 
8  Trend transfer 2 
No.: 
is the consecutive number displayed in WinCC 
flexible ES. 
Check the configuration. 
190101  The area pointer is not updated because it is not 
possible to map the PLC type in the area pointer 
type. 
Parameter type and no.: 
see alarm 190100 
- 
190102  The area pointer is updated following an error 
status after the cause of the last error state has 
been eliminated (return to normal operation). 
Parameter type and no.: See alarm 190100. 
- 
200000  Coordination is not executed because the address 
configured in the PLC does not exist/has not been 
set up. 
Change the address or set up the address in the PLC. 
200001  Coordination is not executed because the address 
configured in the PLC does not exist/has not been 
written. 
Change the address or set up the address in the PLC in 
an area which can be written to. 
200002  Coordination is currently not being performed 
because the address format of the area pointer 
does not match the internal storage format. 
Internal error 
200003  Coordination can be executed again because the 
last error status has been eliminated (return to 
normal operation). 
- 
200004  The coordination may not be executed.  - 
200005  No additional data is read or written. Possible 
causes: 
•  The cable is defective. 
•  The PLC does not respond, is defective, etc. 
•  The system is overloaded. 
Check that the cable is plugged in and the PLC is 
operational. 
Reboot the system if the system alarm is displayed 
continuously. 
200100  Coordination is not executed because the address 
configured in the PLC does not exist/has not been 
set up. 
Change the address or set up the address in the PLC. 
200101  Coordination is not executed because the address 
configured in the PLC does not exist/has not been 
written. 
Change the address or set up the address in the PLC in 
an area which can be written to. 
200102  Coordination is currently not being performed 
because the address format of the area pointer 
does not match the internal storage format. 
Internal error