Introduction & Specifications
SIMPRO-100
26 PRIM-2400C
1.9.3 Reporting Functions
Event Summaries/Event Reports
14 Latest Summaries and 15-Cycle
Oscillographic Records
Resolution: 4 or 16 samples/cycle
Load Profile Function
Stores up to 17 quantities every 15 minutes for 48
days (without voltage option) or 34 days (with
voltage option).
Sequential Events Records
512 Latest Time-Tagged Events
Motor Start Reports
5 Latest Starts
Report Length: 3600 cycles
Quantities stored every 5 cycles during and
immediately after each start.
Motor Start Trend
Stores 30-day averages of starting data for each
of the past eighteen 30-day periods.
1.9.4 Ratings, Type Tests, &
Certifications
Operating Temperature Range
– 40°C to + 85°C
– 40°F to + 185°F
Power Supply Voltage Range
20 – 250 ± 20% Vdc
95 – 240 ± 10% Vac 50/60 Hz
< 15 VA Total Burden
Hold-Up Time: 50 ms @ 125 Vdc
150 ms @ 120 Vac
Type Tests
Front Panel: NEMA12/IP54
Dielectric: 2.5 kV rms, 1 minute
Environmental: IEC 68-2-1 : 1990
IEC 68-2-2 : 1974
Damp Heat Cycle: IEC 68-2-30 : 1980
Impulse: IEC 255-5 : 1977, 5 kV 0.5 j
Electrostatic
Discharge: IEC 801-2 : 1991, Level 4
IEC 255-22-2 : 1989, Level 4
Radio Frequency
Immunity: IEC 801-3 : 1984
IEC 255-22-3 : 1989
Fast Transient
Burst: IEC 801 – 4 : 1988, Level 4
IEC 255-22-4 : 1992,Level 4
Surge Withstand: IEC 255-22-1 : 1988
IEEE C37.90.1 : 1989
5 kV Impulse: IEC 255-5 : 1997
Magnetic Field
Immunity: EN 61000-4-8 : 1993, Level 5
Vibration: IEC 255-21-1 : 1988
Endurance: Class 1
Response: Class 2
Shock and Bump: IEC 255-21-2 : 1988
Bump: Class 1
Shock Withstand: Class 1
Shock Response: Class 2
Seismic: IEC 255-21-3 : 1993, Level 2
Certifications
ISO: Relay is designed and manufactured
to an ISO-9001 certified quality
program.
UL/CSA: UL recognized to the requirements of
UL-508; CSA C22.2, N.14 for
Industrial Control Equipment; and
UL-1053, "Ground-Fault Sensing and
Relay Equipment."
CE: CE Mark.