4
Settings Calculation
SIMPRO-100
50 PRIM-2400C
4.4.1.3 Thermal Element USER Setting Method
Table 4.10 Thermal Element Configuration Settings, Setting Method = USER
When the thermal element setting method is set
to USER, the relay allows you to construct a
custom motor protection curve using as few as 5
or as many as 25 thermal limit points. The relay
requires:
The Full Load Amps and Service Factor
ratings for the motor
Time to Trip settings at 2.00 and 2.50 times
Full Load Amps for overload protection
Time to Trip settings at 5.50, 6.00, and 6.50
times Full Load Amps for locked rotor
protection
Setting Prompt Setting Range
Setting Name =
Example Setting
Setting Method Rating, Generic, User SETMETH = USER
Full Load Amps 2.50 – 8.00 A ITAP = 5 A
0.50 – 1.60 A ITAP = 1A
FLA = 3.66
FLA = 0.732
Service Factor 1.00 – 1.50 SF = 1.25
Time to Trip at 1.05 • FLA 1.0 – 6000.0 s, NP TTT105 = NP
Time to Trip at 1.10 • FLA 1.0 – 6000.0 s, NP TTT110 = NP
Time to Trip at 1.20 • FLA 1.0 – 6000.0 s, NP TTT120 = NP
Time to Trip at 1.30 • FLA 1.0 – 6000.0 s, NP TTT130 = NP
Time to Trip at 1.40 • FLA 1.0 – 6000.0 s, NP TTT140 = NP
Time to Trip at 1.50 • FLA 1.0 – 6000.0 s, NP TTT150 = NP
Time to Trip at 1.75 • FLA 1.0 – 6000.0 s, NP TTT175 = NP
Time to Trip at 2.00 • FLA 1.0 – 6000.0 s TTT200 = NP
Time to Trip at 2.25 • FLA 1.0 – 6000.0 s, NP TTT225 = NP
Time to Trip at 2.50 • FLA 1.0 – 6000.0 s TTT250 = NP
Time to Trip at 2.75 • FLA 1.0 – 6000.0 s, NP TTT275 = NP
Time to Trip at 3.00 • FLA 1.0 – 6000.0 s, NP TTT300 = NP
Time to Trip at 3.50 • FLA 1.0 – 6000.0 s, NP TTT350 = NP
Time to Trip at 4.00 • FLA 1.0 – 6000.0 s, NP TTT400 = NP
Time to Trip at 4.50 • FLA 1.0 – 6000.0 s, NP TTT450 = NP
Time to Trip at 5.00 • FLA 1.0 – 600.0 s, NP TTT500 = NP
Time to Trip at 5.50 • FLA 1.0 – 600.0 s TTT550 = NP
Time to Trip at 6.00 • FLA 1.0 – 600.0 s TTT600 = NP
Time to Trip at 6.50 • FLA 1.0 – 600.0 s TTT650 = NP
Time to Trip at 7.00 • FLA 1.0 – 450.0 s, NP TTT700 = NP
Time to Trip at 7.50 • FLA 1.0 – 400.0 s, NP TTT750 = NP
Time to Trip at 8.00 • FLA 1.0 – 400.0 s, NP TTT800 = NP
Time to Trip at 8.50 • FLA 1.0 – 350.0 s, NP TTT850 = NP
Time to Trip at 9.00 • FLA 1.0 – 300.0 s, NP TTT900 = NP
Time to Trip at 10.00 • FLA 1.0 – 225.0 s, NP TTT1000 = NP