4.4.1.3 Thermal Element USER Setting Method
Table 4.10 Thermal Element Configuration Settings, Setting Method = USER
When the thermal element setting method is set
to USER, the relay allows you to construct a
custom motor protection curve using as few as 5
or as many as 25 thermal limit points. The relay
requires:
• The Full Load Amps and Service Factor
ratings for the motor
• Time to Trip settings at 2.00 and 2.50 times
Full Load Amps for overload protection
• Time to Trip settings at 5.50, 6.00, and 6.50
times Full Load Amps for locked rotor
protection
Setting Prompt Setting Range
Setting Name =
Example Setting
Setting Method Rating, Generic, User SETMETH = USER
Full Load Amps 2.50 – 8.00 A ITAP = 5 A
0.50 – 1.60 A ITAP = 1A
FLA = 3.66
FLA = 0.732
Service Factor 1.00 – 1.50 SF = 1.25
Time to Trip at 1.05 • FLA 1.0 – 6000.0 s, NP TTT105 = NP
Time to Trip at 1.10 • FLA 1.0 – 6000.0 s, NP TTT110 = NP
Time to Trip at 1.20 • FLA 1.0 – 6000.0 s, NP TTT120 = NP
Time to Trip at 1.30 • FLA 1.0 – 6000.0 s, NP TTT130 = NP
Time to Trip at 1.40 • FLA 1.0 – 6000.0 s, NP TTT140 = NP
Time to Trip at 1.50 • FLA 1.0 – 6000.0 s, NP TTT150 = NP
Time to Trip at 1.75 • FLA 1.0 – 6000.0 s, NP TTT175 = NP
Time to Trip at 2.00 • FLA 1.0 – 6000.0 s TTT200 = NP
Time to Trip at 2.25 • FLA 1.0 – 6000.0 s, NP TTT225 = NP
Time to Trip at 2.50 • FLA 1.0 – 6000.0 s TTT250 = NP
Time to Trip at 2.75 • FLA 1.0 – 6000.0 s, NP TTT275 = NP
Time to Trip at 3.00 • FLA 1.0 – 6000.0 s, NP TTT300 = NP
Time to Trip at 3.50 • FLA 1.0 – 6000.0 s, NP TTT350 = NP
Time to Trip at 4.00 • FLA 1.0 – 6000.0 s, NP TTT400 = NP
Time to Trip at 4.50 • FLA 1.0 – 6000.0 s, NP TTT450 = NP
Time to Trip at 5.00 • FLA 1.0 – 600.0 s, NP TTT500 = NP
Time to Trip at 5.50 • FLA 1.0 – 600.0 s TTT550 = NP
Time to Trip at 6.00 • FLA 1.0 – 600.0 s TTT600 = NP
Time to Trip at 6.50 • FLA 1.0 – 600.0 s TTT650 = NP
Time to Trip at 7.00 • FLA 1.0 – 450.0 s, NP TTT700 = NP
Time to Trip at 7.50 • FLA 1.0 – 400.0 s, NP TTT750 = NP
Time to Trip at 8.00 • FLA 1.0 – 400.0 s, NP TTT800 = NP
Time to Trip at 8.50 • FLA 1.0 – 350.0 s, NP TTT850 = NP
Time to Trip at 9.00 • FLA 1.0 – 300.0 s, NP TTT900 = NP
Time to Trip at 10.00 • FLA 1.0 – 225.0 s, NP TTT1000 = NP