EasyManua.ls Logo

Siemens SIMPRO-100 - Table 4.12 Thermal Capacity Alarm Setting; Table 4.13 Thermal Capacity to Start Settings; Table 4.14 Motor Cooling Time Settings

Siemens SIMPRO-100
240 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
SIMPRO-100
Settings Calculation
4
PRIM-2400C 53
4.4.1.4 Thermal Capacity Alarm Setting
Table 4.12 Thermal Capacity Alarm Setting
For all thermal element settings methods, the
relay provides a thermal alarm. When the motor
thermal capacity used exceeds the Thermal
Capacity Alarm Pickup (TCAPU), the relay issues
an alarm. The early alarm may allow you to
correct the load problem before a thermal trip
occurs.
4.4.1.5 Thermal Capacity to Start
Settings
Table 4.13 Thermal Capacity to Start Settings
The motor tripping and starting functions include
supervision to help prevent a thermal trip on a
normal start. The relay prevents motor starting
until the thermal element has enough available
thermal capacity to allow a motor start without
tripping. The available thermal capacity required
to start is (100% – 10% – TCSTART), where the
Thermal Capacity Used To Start (TCSTART)
setting or the relay can learn a value.
When you use the Use Learned Starting Thermal
Capacity function (TCLRNEN = Y), the relay
records the thermal capacity used during the past
five starts and uses it in the thermal model in
place of the Thermal Capacity Used to Start
setting. The relay adds 10% to the largest of the
last five starting thermal capacities and requires
that the motor thermal model cool enough to
permit that start.
Example: Learned Starting Thermal Capacity
Calculation
Over the past five starts, a motor has used
24%, 27%, 22%, 25%, and 26% of thermal
capacity. The largest thermal capacity to
start is 27%. The relay requires that the
present thermal capacity drop below 63%
(100% – 37%) before a new start is
allowed.
You can view the present learned thermal
capacity to start using the serial port MOTOR
command or the front-panel Motor
Statistics\Average and Peak Data Function (see
Figure 5.29, page 82.
4.4.1.6 Motor Cooling Time Settings
Table 4.14 Motor Cooling Time Settings
A stopped motor may take longer to cool than a
running motor due to reduced airflow or loss of
forced coolant. The factory default settings
assume that the motor stopped cooling time is
twice the motor running cooling time. Based on
the setting names, the equation is:
Equation 4.2
You can take similar steps to calculate the
COOLTIME setting for your application.
Motor running and stopped cooling times or time
constants may be provided by the motor
manufacturer. If a time constant is provided,
multiply that value by 3 to calculate the Motor
Stopped Cooling Time (COOLTIME) setting.
Setting Prompt
Setting
Range
Setting Name =
Factory Default
Thermal Capacity
Alarm Pickup
50% – 100% TCAPU = 90
Setting Prompt
Setting
Range
Setting Name =
Factory Default
Thermal Capacity
Used to Start
20% – 100% TCSTART = 85
Use Learned Starting
Thermal Capacity
Y, N TCLRNEN = Y
Setting Prompt
Setting
Range
Setting Name =
Factory Default
Motor Stopped
Cooling Time
180 – 72000 s COOLTIME = 259
Use Learned
Cooling Time
Y, N COOLEN = Y

Table of Contents

Related product manuals