The relay allows you to define the type of each
monitored RTD independently using the RTD
Type settings.
If an RTD Location setting is equal to NONE, the
relay does not request that an RTD Type setting
be entered for that input.
The four available RTD types are:
100-ohm platinum (PT100)
100-ohm nickel (NI100)
120-ohm nickel (NI120)
10-ohm copper (CU10)
4.5.4 RTD Alarm & Trip
Temperatures
Table 4.26 RTD Alarm and Trip Temperature Settings
Setting Prompt Setting Range
Setting Name =
Factory Default
RTD Trip Temperature OFF, 32° – 482°F TRTMP1 = OFF
RTD Alarm Temperature OFF, 32° – 482°F ALTMP2 = OFF
RTD Trip Temperature OFF, 32° – 482°F TRTMP2 = OFF
RTD Alarm Temperature OFF, 32° – 482°F ALTMP2 = OFF
RTD Trip Temperature OFF, 32° – 482°F TRTMP3 = OFF
RTD Alarm Temperature OFF, 32° – 482°F ALTMP3 = OFF
RTD Trip Temperature OFF, 32° – 482°F TRTMP4 = OFF
RTD Alarm Temperature OFF, 32° – 482°F ALTMP4 = OFF
RTD Trip Temperature OFF, 32° – 482°F TRTMP5 = OFF
RTD Alarm Temperature OFF, 32° – 482°F ALTMP5 = OFF
RTD Trip Temperature OFF, 32° – 482°F TRTMP6 = OFF
RTD Alarm Temperature OFF, 32° – 482°F ALTMP6 = OFF
RTD Trip Temperature OFF, 32° – 482°F TRTMP7 = OFF
RTD Alarm Temperature OFF, 32° – 482°F ALTMP7 = OFF
RTD Trip Temperature OFF, 32° – 482°F TRTMP8 = OFF
RTD Alarm Temperature OFF, 32° – 482°F ALTMP8 = OFF
RTD Trip Temperature OFF, 32° – 482°F TRTMP9 = OFF
RTD Alarm Temperature OFF, 32° – 482°F ALTMP9 = OFF
RTD Trip Temperature OFF, 32° – 482°F TRTMP10 = OFF
RTD Alarm Temperature OFF, 32° – 482°F ALTMP10 = OFF
RTD Trip Temperature OFF, 32° – 482°F TRTMP11 = OFF
RTD Alarm Temperature OFF, 32° – 482°F ALTMP11 = OFF
RTD Trip Temperature
b
OFF, 32° – 482°F TRTMP12 = OFF
RTD Alarm
Temperature
b
OFF, 32° – 482°F ALTMP12 = OFF
Enable Winding Trip
Voting
Y, N E W N D G V = N
Enable Bearing Trip
Voting
Y, N EBRNGV = N
Enable RTD Biasing Y, N RTDBEN = Y
a
Note: When the TEMPREF setting equals C, the trip and alarm
temperature setting ranges above are: OFF, 0
° –
250°C.
b
The twelfth RTD input is only available when you use the
SIMPRO-100-RTD External RTD Module.