SIMPRO-100
Maintenance & Troubleshooting
10
PRIM-2400C 133
f. Issue a STA command and verify that
relay status is OK.
g. Set the relay clock and calendar using the
DATE and TIME commands.
h. Set the Relay, Port, and SER settings
using the SIMPRO-PC software or the
following commands: SET, SET P F, SET
P R, SET R.
i. Set the relay passwords via the PAS
command.
13. Execute the STATUS command to verify all
relay self-test results are okay.
14. Apply current and voltage signals to the relay.
Issue the METER command; verify that
current and voltage signals are correct. Issue
the TRIGGER and EVENT commands. Verify
that current and voltage signals are correct in
the EVENT report.
The relay is now ready for your commissioning
procedure.