Cabinet Modules
5.1 Line Connection Modules
Cabinet Modules NEMA
136 Manual, 04/2014, A5E03586450A
Table 5- 4 Factory setting of the overcurrent release on Line Connection Modules for Smart Line Modules
Order number
Line Connection
Module
Order number
Smart Line Module
Input current
Line Module
Overload trip
(L)
Short-time de-
layed short-
circuit release
(S)
Delay time short-
circuit release
(t
sd
)
6SL3700-0LE41-0AU3
6SL3730-6TE41-1AU3
883 A
1.0
2
0
6SL3700-0LE41-3AU3
6SL3730-6TE41-3AU3
1093 A
1.0
2
0
6SL3700-0LE41-6AU3
6SL3730-6TE41-7AU3
1430 A
1.0
2
0
6SL3700-0LE42-0BU3 6SL3730-6TE41-1xU3 2 x 817 A 0.9 2 0
6SL3700-0LE42-5BU3
6SL3730-6TE41-3xU3
2 x 1011 A
0.9
2
0
6SL3700-0LE43-2BU3
6SL3730-6TE41-7xU3
2 x 1323 A
0.9
2
0
6SL3700-0LG41-3AU3
6SL3730-6TG41-2AU3
1009 A
0.9
2
0
6SL3700-0LG41-6AU3
6SL3730-6TG41-7AU3
1430 A
1.0
2
0
6SL3700-0LG42-0BU3
6SL3730-6TG38-8xU3
2 x 700 A
0.8
2
0
6SL3700-0LG42-0BU3
6SL3730-6TG41-2xU3
2 x 934 A
1.0
2
0
6SL3700-0LG43-2BU3
6SL3730-6TG41-7xU3
2 x 1323 A
0.9
2
0
Table 5- 5 Factory setting of the overcurrent release on Line Connection Modules for Active Line Modules
Order number
Line Connection
Module
Order number
Active Line Module
Input current
Line Module
Overload trip
(L)
Short-time de-
layed short-
circuit release
(S)
Delay time short-
circuit release
(t
sd
)
6SL3700-0LE41-0AU3
6SL3730-7TE38-4AU3
840 A
1.0
2
0
6SL3700-0LE41-3AU3
6SL3730-7TE41-0AU3
985 A
0.9
2
0
6SL3700-0LE41-6AU3
6SL3730-7TE41-4AU3
1405 A
1.0
2
0
6SL3700-0LE42-0BU3
6SL3730-7TE41-0xU3
2 x 936 A
1.0
2
0
6SL3700-0LE43-2BU3
6SL3730-7TE41-4xU3
2 x 1335 A
0.9
2
0
6SL3700-0LG41-3AU3
6SL3730-7TG41-0AU3
1025 A
0.9
2
0
6SL3700-0LG41-6AU3
6SL3730-7TG41-3AU3
1270 A
0.9
2
0
6SL3700-0LG42-0BU3
6SL3730-7TG37-4xU3
2 x 698 A
0.7
2
0
6SL3700-0LG42-0BU3
6SL3730-7TG41-0xU3
2 x 974 A
1.0
2
0
6SL3700-0LG42-5BU3 6SL3730-7TG41-3xU3 2 x 1206 A 1.0 2 0
NOTICE
Property damage due to incorrect setting of the overcurrent release
Incorrect settings can cause unwanted or delayed tripping of the circuit breaker and result
in excessive damage to the cabinet unit.
Check the above-indicated settings and, if necessary, adapt the settings to the system
configuration.