Cabinet Modules
5.1 Line Connection Modules
Cabinet Modules NEMA
Manual, 04/2014, A5E03586450A
137
Note
Additional information
Detailed and comprehensive instructions and information for the circuit breaker as well as
the
standard and additional options can be found in the enclosed operating instructions,
These operating instructions are available as additional documentation on the customer DVD
supplied with the device.
X50 "circuit breaker" checkback contact
Table 5- 6 Terminal block X50 "Circuit breaker" checkback contact
Terminal
Designation
1)
Technical specifications
1 NO "Circuit breaker" checkback contacts
Max. load current: 3 A
Max. switching voltage: 250 V AC
2
NC
3
COM
Max. connectable cross-section #14 AWG (2.5 mm²)
1)
NC: normally-closed contact, NO: normally-open contact, COM: mid-position contact
X30 looping in an external EMERGENCY OFF
Terminal block -X30 provides you with the option of connecting an external EMERGENCY
OFF (normally-closed contact) for switching off the circuit breaker.
Table 5- 7 Terminal block X30 "External EMERGENCY OFF" checkback contact
Terminal
Technical specifications
1
Factory-installed jumper between terminal 1 and terminal 2; this jumper must be re-
moved if a normally-closed contact is looped in externally.
2
Max. connectable cross-section #14 AWG (2.5 mm²)