Cabinet Modules
5.4 Active Line Modules including Active Interface Modules
Cabinet Modules NEMA
Manual, 04/2014, A5E03586450A
199
Order no.
6SL3730-
7TG35-
8AU3
7TG37-
4AU3
7TG41-
0AU3
7TG41-
3AU3
Weight
(standard model) lb
kg
2050
930
3000
1360
3000
1360
3000
1360
Frame size
HX + HI JX + JI JX + JI JX + JI
SCCR (short circuit current rating)
kA IC
65
84
100
100
Minimum short-circuit current
7)
A 9000 15000
4000
2500
4000
3200
5000
1)
The base load current I
H DC
is based on a duty cycle of 150 % for 60 s or I
max DC
for 5 s with a duty cycle duration of
300 s.
2)
The current demand for the 500/690 V AC auxiliary supply is provided by the supply input voltage.
3)
The specified power loss represents the maximum value at 100 % capacity utilization. The value in normal operation is
lower.
4)
Total sound pressure level of Active Interface Module and Active Line Module.
5)
Total of all motor cables and DC link. Longer cable lengths for specific configurations are available on request, see
SINAMICS - Low Voltage Configuration Manual on the customer DVD supplied with the device.
6)
The cabinet height increases by 10" (250 mm) with degree of protection IP21, and by 16" (400 mm) with degrees of
protection IP23 (NEMA1 filtered), IP43, and IP54 (NEMA12 ventilated).
7)
Minimum current required for reliable tripping of the contained protective devices.