8.3 Description of parameters
8.3.1 Initialization parameters 1 to 5
8.3.1.1 '1.YFCT' type of actuator
Requirement: Type of actuator as well as mounting type and direction of action are
known.
Possible settings:
Actuator with normal direction
of action
Actuator with inverted direction of
action
turn
WAY
FWAY
LWAY
ncSt
ncSL
ncSLL
-turn
-WAY
-FWAY
-LWAY
-ncSt
-ncSL
-ncLL
Purpose: Use this parameter to adjust the positioner to the respective actua‐
tor.
turn/-turn: Use this setting for a part-turn actuator with a directly
mounted positioner.
WAY/-WAY: Use this setting.
For a linear actuator with a carrier pin mounted on the lever.
In conjunction with devices which use an internal
potentiometer.
FWAY/-FWAY: Use this setting.
For a linear actuator with a carrier pin mounted on the
actuator spindle.
In conjunction with devices which use an internal
potentiometer.
LWAY/-LWAY: Use this setting for an external linear
potentiometer on a linear actuator (e.g. with cylinder drives).
ncSt/-ncSt: Use this setting for a part-turn actuator for:
An NCS sensor 6DR4004-. N.10 and -.N.40
A positioner 6DR5...-0..9.-....- L1A with internal NCS module
A positioner 6DR59* with accessory NCS module
6DR4004-5L/-5LE
External position detection systems 6DR4004-2ES, -3ES
and -4ES
Internal NCS module
ncSL/-ncSL: Use this setting for an NCS sensor 6DR4004-.N.20
on a linear actuator for strokes < 14 mm (0.55 inch).
Parameter assignment
8.3 Description of parameters
SIPART PS2 with PROFIBUS PA
142 Operating Instructions, 05/2019, A5E00127926-AC