EasyManua.ls Logo

Siemens SIPART PS2 - Corrective Measures Table 3; Corrective Measures Table 4

Siemens SIPART PS2
372 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
12.4.4 Corrective measures Table 3
Fault profile (symptoms) Possible cause Corrective measures
Actuator does not move. Compressed air < 1.4 bar Set pressure of supply air PZ to
> 1.4 bar.
Piezo valve does not switch
(however, a gentle clicking sound
can be heard when the or
button is pressed in "Manual" mode.)
Restrictor valve turned off (screw at
the right endstop)
Open the restrictor screw by turning
it anticlockwise, see leaflet, Fig.
"Device view ".
Dirt in the pneumatic block Repair or a new device; clean and/or
replace the built-in fine screens.
A piezo valve is switched constantly
in stationary automatic mode
(constant setpoint) and in "Manual"
mode.
Pneumatic leakage in the positioner
- actuator system; start the leakage
test in "RUN 3" (initialization).
Rectify leakage in the actuator
and/or feed line.
In case of an intact actuator and tight
feed line: Repair or new device
Dirt in the pneumatic block See above
Fault table 3
See also
Repair/Upgrading (Page 244)
12.4.5 Corrective measures Table 4
Fault profile (symptoms) Possible cause(s) Corrective measures
In stationary automatic mode
(constant setpoint) and in "Manual"
mode, both piezo valves continually
switch alternately, and the actuator
oscillates around an average value.
Stiction of the packing gland from
the control valve or actuator too large
Reduce stiction or increase
deadband of positioner (parameter
"dEbA") until the oscillation stops.
Looseness (play) in the positioner/
actuator/control valve system
Part-turn actuator: Check for firm
seating of set screw on coupling
wheel.
Linear actuator: Check for firm
seating of lever on positioner shaft.
Correct any other play between the
actuator and the control valve.
Actuator too fast Increase travel times using throttle
screws.
If a quick travel time is needed,
increase the deadband (parameter
"dEbA") until the oscillation stops.
Positioner doesn't move control
valve to the stop (at 20 mA).
Supply pressure too low. Load on
the feeding controller or system
output is too low.
Increase supply pressure, insert
ballast converter
Select 3/4-wire mode
Error table 4
Diagnostics and troubleshooting
12.4 Fault correction
SIPART PS2 with PROFIBUS PA
Operating Instructions, 05/2019, A5E00127926-AC 279

Table of Contents

Other manuals for Siemens SIPART PS2

Related product manuals