WARNING
Improper connection after maintenance
Risk of explosion in areas subject to explosion hazard.
Connect the device correctly after maintenance.
Close the device after maintenance work.
Refer to Connect (Page 77).
11.3.2 Repair/Upgrading
Send defective devices to the repairs department, together with information on the malfunction
and the cause of the malfunction. When ordering replacement devices, please provide the
serial number of the original device. You can find the serial number on the nameplate.
See also
Nameplate layout (Page 26)
Technical support (Page 307)
11.4 Replace basic electronics
Requirements
You are familiar with the general procedure described in the section "General information
about the installation of option modules (Page 53)".
Procedure
Note
Possible Movement of the Drive
While replacing the basic electronics, the drive can unintentionally vent itself.
Observe the procedure described below.
Removing
1. Switch off the supply air PZ and depressurize the actuator.
2. Open the positioner as in the description depending on the device version:
Opening the standard and and intrinsically safe version (Page 53)
Opening the device version with "flameproof enclosure" (Page 56)
Service and maintenance
11.4 Replace basic electronics
SIPART PS2 with PROFIBUS PA
244 Operating Instructions, 05/2019, A5E00127926-AC

Table of Contents

Other manuals for Siemens SIPART PS2

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIPART PS2 and is the answer not in the manual?

Siemens SIPART PS2 Specifications

General IconGeneral
Supply Pressure1.4 to 7 bar (20 to 100 psi)
Enclosure RatingIP66/NEMA 4X
Communication ProtocolsHART, PROFIBUS PA, FOUNDATION Fieldbus
Output Pressure0 to 100% of supply pressure
Hazardous Area CertificationATEX, IECEx, FM, CSA
TypeElectropneumatic
Input Signal4-20 mA
Rotation Angle30° to 90°
Operating Temperature-40°C to +80°C
MountingLinear and rotary actuators
Air ConsumptionTypically less than 0.1 kg/h