To optimize the sensitivity of the monitoring of the pneumatic leak‐
age to your specific application, follow these steps:
1. After initializing the positioner automatically, use a calibration
device to initiate a ramp movement.
2. Conditions for the ramp movement:
The ramp covers the normal operating range of the valve.
The steepness of the ramp matches the dynamic
requirements of the corresponding application.
The characteristic of the ramp corresponds to the
characteristic of the setpoint that actually occurs.
3. During the ramp movement, the Diagnostic value '16.ONLK -
Pneumatic leakage' (Page 263) provides information about the
actual values. Define the limit of the leakage indicator
accordingly.
The positioner triggers a message if the current value exceeds one
of the three thresholds. How to set the three thresholds is described
below.
Factory setting: 30.0
C2.FACT1 - Factor 1
Adjustment range: 0.1 ... 100.0
Purpose: Use this sub-parameter to set the factor for formation of threshold 1.
Set the factor in a range from '0.1' to '100.0'. The threshold is the
product of 'C1.LIMIT' and 'C2.FACT1'.
A leakage was detected when threshold 1 is exceeded. The control
quality is not affected. The threshold 1 message is shown. This
message is only output if threshold 2 or 3 is not exceeded at the
same time.
The process to activate and display this message is described in the
'XDIAG' parameter.
Factory setting: 1.0
C3.FACT2 - Factor 2
Adjustment range: 0.1 ... 100.0
Purpose: Use this sub-parameter to set the factor for formation of threshold 2.
Set the factor in a range from '0.1' to '100.0'. The threshold is the
product of 'C1.LIMIT' and 'C3.FACT2'.
A leakage was detected when threshold 2 is exceeded. The control
quality is affected. Maintenance is recommended. The threshold 2
message is shown. This message is only output if threshold 3 is not
exceeded at the same time.
The process to activate and display this message is described in the
'XDIAG' parameter.
Factory setting: 1.5
Parameter assignment
8.3 Description of parameters
SIPART PS2 with PROFIBUS PA
172 Operating Instructions, 05/2019, A5E00127926-AC

Table of Contents

Other manuals for Siemens SIPART PS2

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIPART PS2 and is the answer not in the manual?

Siemens SIPART PS2 Specifications

General IconGeneral
Supply Pressure1.4 to 7 bar (20 to 100 psi)
Enclosure RatingIP66/NEMA 4X
Communication ProtocolsHART, PROFIBUS PA, FOUNDATION Fieldbus
Output Pressure0 to 100% of supply pressure
Hazardous Area CertificationATEX, IECEx, FM, CSA
TypeElectropneumatic
Input Signal4-20 mA
Rotation Angle30° to 90°
Operating Temperature-40°C to +80°C
MountingLinear and rotary actuators
Air ConsumptionTypically less than 0.1 kg/h