EasyManuals Logo

Siemens SIPART PS2 User Manual

Siemens SIPART PS2
372 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #181 background imageLoading...
Page #181 background image
Purpose: The current temperature inside the enclosure of the field device is
recorded by a sensor on the basic electronics. Use this parameter
to activate continuous monitoring of the upper limit temperature
inside the enclosure. Monitoring is performed in three steps. To
activate monitoring, set the parameter to 'On'. Sub-parameters are
displayed. Appropriately set the sub-parameters.
The value is displayed in Diagnostic value '31.TMIN - Minimum
temperature' / '32.TMAX - Maximum temperature' (Page 268). The
positioner triggers a message if the current value exceeds one of
the three thresholds.
Factory setting: OFF
J1.TUNIT - temperature unit
Possible settings: °C
°F
Purpose: Use this sub-parameter to set the temperature unit '°C' or '°F'. The
selected temperature unit is then also applicable for all other tem‐
perature-based parameters.
Factory setting: °C
J2.LEVL1 - threshold 1
Adjustment range: -40.0C ... 90.0C
-40.0F ... 194.0F
Purpose: Use this sub-parameter to set the temperature for threshold 1.
The positioner triggers a threshold 1 message if the current tem‐
perature inside the enclosure exceeds threshold 1. This message is
only output if threshold 2 or 3 is not exceeded at the same time. The
process to activate and display this message is described in the
'XDIAG' parameter.
Factory setting: 75.0C
J3.LEVL2 - threshold 2
Adjustment range: -40.0C ... 90.0C
-40.0F ... 194.0F
Purpose: Use this sub-parameter to set the temperature for threshold 2.
The positioner triggers a threshold 2 message if the current tem‐
perature inside the enclosure exceeds threshold 2. This message is
only output if threshold 3 is not exceeded at the same time. The
process to activate and display this message is described in the
'XDIAG' parameter.
Factory setting: 80.0C
Parameter assignment
8.3 Description of parameters
SIPART PS2 with PROFIBUS PA
Operating Instructions, 05/2019, A5E00127926-AC 181

Table of Contents

Other manuals for Siemens SIPART PS2

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIPART PS2 and is the answer not in the manual?

Siemens SIPART PS2 Specifications

General IconGeneral
Supply Pressure1.4 to 7 bar (20 to 100 psi)
Enclosure RatingIP66/NEMA 4X
Communication ProtocolsHART, PROFIBUS PA, FOUNDATION Fieldbus
Output Pressure0 to 100% of supply pressure
Hazardous Area CertificationATEX, IECEx, FM, CSA
TypeElectropneumatic
Input Signal4-20 mA
Rotation Angle30° to 90°
Operating Temperature-40°C to +80°C
MountingLinear and rotary actuators
Air ConsumptionTypically less than 0.1 kg/h

Related product manuals