Purpose: Use this parameter to continuously monitor the number of changes
in direction of the actuator beyond the deadband. Monitoring is per‐
formed in three steps. Set the following sub-parameters appropri‐
ately. To activate monitoring, set the parameter to 'On'. Sub-pa‐
rameters are displayed.
The current value is displayed in Diagnostic value '2.CHDIR - Num‐
ber of changes in direction' (Page 259). The positioner triggers a
message if the current value exceeds one of the three thresholds.
Factory setting: OFF
O1.LIMIT - Limit
Adjustment range: 1 ... 1.00E8
Purpose: Use this sub-parameter to set the base limit for the changes of
direction of the actuator. Set the base limit in a range from '1' to
'1.00E8'.
Factory setting: 1.00E6
O2.FACT1 - Factor 1
Adjustment range: 0.1 ... 40.0
Purpose: Use this sub-parameter to set the factor for formation of threshold 1.
Set the factor in a range from '0.1' to '40.0'. The threshold is the
product of 'O1.LIMIT' and 'O2.FACT1'.
The threshold 1 message is displayed when threshold 1 is excee‐
ded. This message is only output if threshold 2 or 3 is not exceeded
at the same time. The process to activate and display this message
is described in the 'XDIAG' parameter.
Factory setting: 1.0
O3.FACT2 - Factor 2
Adjustment range: 0.1 ... 40.0
Purpose: Use this sub-parameter to set the factor for formation of threshold 2.
Set the factor in a range from '0.1' to '40.0'. The threshold is the
product of 'O1.LIMIT' and 'O3.FACT2'.
The threshold 2 message is displayed when threshold 2 is excee‐
ded. This message is only output if threshold 3 is not exceeded at
the same time. The process to activate and display this message is
described in the 'XDIAG' parameter.
Factory setting: 2.0
Parameter assignment