The DP interface is equipped with one system interface for connecting the safety relay and
one device interface for connecting a PC/PG (sealable).
The DP interface can be used to link non-safety-related signals of a higher-level controller
with the safety relay logic.
The DP interface supports a baud rate of up to 12 Mbps.
Process and diagnostics data can be exchanged through the DP interface:
Cyclic: Depending on the safety relay, the PLC can exchange 32 bits or 64 bits of process
data with safety relay.
Acyclic: The PLC can query diagnostics data data from the safety relay. With Safety ES, the
diagnostics information can be displayed graphically.
Both options can be used at the same time.
The DP interface supports DPV1 and DPV0 mode.
Note
Program cycle time
When the 3SK2 safety relays with product version E01 are operated with a DP interface, set a
program cycle time of 15 ms.
You will 󹪝nd further information in Chapter "Using data sets (Page 288)".
Design of the DP interface module
Front view No. Meaning

'3,QWHUIDFH
Removable terminal block D
Removable terminal block C
System interface (X2)
PROFIBUS DP connection
Removable terminal block A
SET and MODE keys for
operating the device display
Label
LCD display
Display LEDs
Connection of PC / PG, diagnostics display
(X1)
Description of the hardware
5.1 Description of the individual modules
SIRIUS 3RK3 Modular Safety System
118 Equipment Manual, 07/2020, NEB926253002000/RS-AC/006