Messages for safety shutdown mat (cross-circuit principle)
The following table shows the messages with the associated byte arrangement in the element
data block of the "safety shutdown mat with cross-circuit principle" function element.
Byte posi‐
tion
Message Meaning Element status Cyclic data
6
0
Startup test required This message is set in a parameter‐
ized startup test on each restart and
each time the substitute value is
changed to a real value until the
connected sensor is actuated at
least once.
SVW SVW
6
1
... 6
2
Reserved=0
6
3
Safety sensor triggered The safety sensor has been actu‐
ated.
SVW SVW
6
4
... 6
7
Reserved=0
7
0
Wire break at input 1 A cross-circuit was detected at input
1.
Wiring error SF
7
1
Short circuit to P at input 1 A short-circuit to P was detected at
input 1.
Wiring error SF
7
2
... 7
3
Reserved=0
7
4
Wire break at input 2 A cross-circuit was detected at input
2.
Wiring error SF
7
5
Short circuit to P at input 2 A short-circuit to P was detected at
input 2.
Wiring error SF
7
6
... 7
7
Reserved=0
8
0
Start signal duration invalid Only with start type "Monitored
start":
The start signal time monitoring el‐
ement detected a violation.
8
1
Start condition not ful󹪝lled is set if:
A sensor test was not executed
in the case of an active startup
test function
The value "1" is not present si‐
multaneously at all available
(parameterized) function in‐
puts (IN1, ...)
A cross-circuit is present
8
2
... 8
7
Reserved=0
Diagnostics / service
7.6 Diagnosis using AS-Interface (CTT2 protocol)
SIRIUS 3RK3 Modular Safety System
320 Equipment Manual, 07/2020, NEB926253002000/RS-AC/006

Table of Contents