Messages for two-hand operation
The following table shows the messages with the associated byte arrangement in the element
data block of the "two-hand operation" function element.
Byte posi‐
tion
Message Meaning Element status Cyclic data
6
0
... 6
1
Reserved=0
6
2
Discrepancy condi‐
tion violated
is set if:
After the discrepancy time
has elapsed, the signal states
at the inputs monitored are
di󹪜erent within one or be‐
tween to two pushbuttons.
The signal states of the inputs
monitored had not all previ‐
ously been reset simultane‐
ously to the value "0" when
they are set to "1"
Logic error SF
6
3
Bushbutton stuck The pushbutton is stuck. Logic error SF
6
4
Do not release both
pushbuttons
The two pushbuttons were not
released simultaneously.
Logic error SF
6
5
... 6
7
Reserved=0
7
0
Cross-circuit at input 1 A cross-circuit was detected at in‐
put 1.
Wiring error SF
7
1
... 7
3
Reserved=0
7
4
Cross-circuit at input 2 A cross-circuit was detected at in‐
put 2.
Wiring error SF
7
5
... 8
0
Reserved=0
8
1
Start condition not ful‐
󹪝lled
is set if:
If both pushbuttons were not
pressed "synchronously," that
is, they were pressed with a
time o󹪜set greater than 0.5 s
A discrepancy condition viola‐
tion is present
The value "1" is not present si‐
multaneously at IN1 ... 2 / 4
A cross-circuit is present
8
2
... 8
7
Reserved=0
9
0
Cross-circuit at input 3 A cross-circuit was detected at in‐
put 3.
Wiring error SF
9
1
... 9
3
Reserved=0
9
4
Cross-circuit at input 4 A cross-circuit was detected at in‐
put 4.
Wiring error SF
9
5
... 9
7
Reserved=0
Diagnostics / service
7.6 Diagnosis using AS-Interface (CTT2 protocol)
SIRIUS 3RK3 Modular Safety System
Equipment Manual, 07/2020, NEB926253002000/RS-AC/006 321