Group errors ③
The following group errors can be diagnosed:
Message Meaning(s)
Conguration error
1)
• Memory module not plugged in
• SC conguration error
3)
• Memory module defective
• Memory module too small
Conguration error
1)
An error occurred during the conguration phase:
• Release denied due to incorrect conguration CRC
• Release canceled due to incorrect conguration release CRC
• Max. number of elements exceeded
• Max. size of memory exceeded
• Program cycle time exceeded
• TARGET≠ACTUAL conguration
• TARGET≠ACTUAL slot expanded conguration
• Invalid parameter value
• Interconnection rule violated
• Data structure incorrect
Safety protocol error
4)
• Multiple ASIsafe code tables
4)
• ASIsafe 8x4-bit code sequence error
4)
• ASIsafe 7x4-bit code sequence error
4)
Wiring error
2)
Faulty wiring of a sensor connection or in the sensor itself.
Logic error
2)
Protection fault: Processing sequence on the sensor not coherent.
Handshake error An error was detected during connection monitoring in test mode.
Group error from user pro‐
gram
2)
At least one error from the user program is present.
SC bus error
3)
Communication via the system interface is interrupted.
3)
SC conguration error
3)
The actual conguration of an existing communication connection does
not match the target conguration. This resulted in an error.
3)
Memory module defective Memory module is defective.
User memory too small More conguration data were transferred to the safety relay than can be
stored in the conguration memory.
1)
Dierent error causes are possible. The cause is displayed by pressing the right key (OK).
2)
Pressing the right key (OK) switches the diagnostics display directly to the relevant function element in
the status menu.
3)
3RK3 only
4)
3RK3 Advanced and 3RK3 ASIsafe only
Diagnostics / service
7.7 Diagnostics with diagnostics display
SIRIUS 3RK3 Modular Safety System
336 Equipment Manual, 07/2020, NEB926253002000/RS-AC/006