Bus errors
The following bus errors can be diagnosed:
Message Meaning
DP bus error Communication via the 󹪝eldbus interface is interrupted.
DP parameterization error An error occurred during parameterization for an existing communica‐
tion connection.
DP con󹪝guration error The actual con󹪝guration of an existing communication connection
does not match the target con󹪝guration. This resulted in an error.
ASi bus error
1)
Communication via the AS‑i interface is interrupted.
1)
ASi parameterization error
1)
An error occurred during parameterization for an existing communica‐
tion connection.
1)
ASi con󹪝guration error
1)
The actual con󹪝guration of an existing communication connection
does not match the target con󹪝guration. This resulted in an error.
1)
SC bus error
2)
Communication via the system interface is interrupted.
2)
SC parameterization error
2)
An error occurred during parameter assignment for an existing com‐
munication connection.
2)
SC con󹪝guration error
2)
The actual con󹪝guration of an existing communication connection
does not match the target con󹪝guration. This resulted in an error.
2)
1)
3RK3 Advanced and 3RK3 ASIsafe only
2)
3RK3 only
Group warning
The following group warnings can be diagnosed:
Message Meaning
Disconnect The monitoring time has been exceeded During monitoring time, the
safety relay has not received any data set from the communication
partner with write access to the safety relay.
Group warning from user pro‐
gram
1)
At least one warning from the user program is present.
Con󹪝guration missing No valid con󹪝guration is stored in the safety relay.
1)
Pressing the right key (OK) switches the diagnostics display directly to the element in the status menu.
Group prewarning
The following group prewarnings can be diagnosed:
Message Meaning
User program stopped. The safety relay is not processing the safety circuit.
Group prewarning from user
program
1)
At least 1 con󹪝gured function element has a group prewarning.
1)
Pressing the right key (OK) switches the diagnostics display directly to the element in the status menu.
Diagnostics / service
7.7 Diagnostics with diagnostics display
SIRIUS 3RK3 Modular Safety System
Equipment Manual, 07/2020, NEB926253002000/RS-AC/006 337

Table of Contents